background image

IST-2293.EA01.01/C

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.15/15

 

 

 

 

TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) ITALY

 

 Tel: 02/26 92 28 90   Fax: 02/21 33 734

 

 

 

 

190 

65 

83 

105 

70 

Ø42 

107 

Fig. 1 –

 

Dimensioni /

 Size / Dimensions 

Imbocco Femmina ¾” Gas Conico UNI 6125 

”¾” UNI 6125 Female Gas Conical Thread 

Entrée femelle ¾” Gaz Conique UNI 6125

 

 

 

12

-2

4V

 

m

A

 

1

 

2

 

3

 

4

 

ON

 

OFF

 

SET

 

+/- 

(12÷24Vdc)

 

Alimentazione / Power Supply / Alimentation

 

Centrale rivelazione gas 

Gas Central Unit

 

Centrale de détection

 

RL

 

-

 

S

 

Dip Switch

 

+

 

Test Uscita  

Output Test 

Sortie Test 

40÷200mV

 

 

TP1   TP2

 

mV

 

“S” - 

Uscita 4÷20 mA 

4÷20 mA Output / Sortie en 4÷20 mA

 

Fig. 2 -

 

Schema di collegamento 

/ Wiring diagram / Schéma

 

 

 

Fig. 3 -

 Tester di calibrazione 

/ Calibration Tester / Kit de Calibration 

0,3 L/ min

 

1 L/ min

 

 

 

Alimentazione 

/ Power Supply / Alimentation

 

100

 

300

 

400

 

500

 

50

 

0

 

5

 

200

 

Vdc

 

RL=Resistenza di carico 

/ Load resistor / Resistance de charge

 

RL

 

Ohm

 

Fig.4 -

 

Alimentazione / Resistenza di Carico 4÷20mA 

Power supply / Load resistance diagram 4÷20mA 
Alimentation / Résistance de charge 4÷20mA

 

600

 

0

 

10

 

15

 

20

 

25

 

28

 

650

 

10,8

 

24

 

Area di funzionamento 

Allowable oparating region 

350

 

700

 

800 

 

 

Summary of Contents for TS293E Series

Page 1: ...de ZS EC2 EX TS293ES SO2 Biossido di zolfo Sulfur dioxide ZS ES1 EX TS293EH H2S Idrogeno Solforato Hydrogen sulphide ZS EH1 EX TS293EHCN HCN Acido cianidrico Hydrogen cyanide ZS EHCN EX TS293EN NO Ossido di azoto Nitric oxide ZS EN1 EX TS293EN2 NO2 Biossido di azoto Dioxyde d azote ZS EN2 EX Con Cartuccia Sensore Sostituibile Inside Replaceable Cartridge Sensor Avec Cartouche Capteur échangeable S...

Page 2: ...nni years ans 2 anni years ans 2 anni years ans 2 anni years ans 2 anni years ans 2 anni years ans Tempo massimo di immagazzinamento Max Storage Time Temps maximum de stockage 3 mesi month mois 1 mese month mois 3 mesi month mois 3 mesi month mois 3 mesi month mois 3 mesi month mois 3 mesi month mois 3 mesi month mois 3 mesi month mois Variazione dello Zero Zero shift Dérive du Zero 6 ppm 4 ppm 10...

Page 3: ... ha densità relativa all aria di 2 25 Il suo TWA è 2 ppm Time Weighted Average e lo STEL è 5 ppm Short Term Exposure Limit L SO2 è un forte irritante per gli occhi e le vie respiratorie Per inalazione può causare edema polmonare e una prolungata esposizione può portare alla morte Nel caso si combini con l acqua forma Idrogeno Solforato H2S TS293EH ha un sensore in grado di rilevare Idrogeno Solfor...

Page 4: ...ilitato il Led rosso e quindi tutti i Led sono accesi uscita 20mA indica o il guasto della Cartuc cia Sensore oppure una concentrazione di gas superiore al Fondo Scala Se non è presente alcuna fuga di gas e la condizione persiste anche dopo la sostituzione della Cartuccia sarà necessario inviare il rilevatore al fornitore per la riparazione INSTALLAZIONE I rilevatori vanno installati posizionati e...

Page 5: ... codice Kit di Taratura e Bombole con Miscela Gas titolato per Calibrazione e Verifica la miscela da utilizzare in funzio ne del modello installato è MODELLO Bombola di Gas Titolato Codice Bombola TS293EA TS293EA H 100 ppm Ammoniaca NH3 in azoto Fornibile a richiesta TS293EC S TS293EC H 300 ppm Monossido di carbonio CO in azoto BO210 TS293ES 10 ppm Biossido di zolfo SO2 in azoto Fornibile a richie...

Page 6: ...to in colonna 3 della tabella ovvero che l uscita in mA aumenti fino al valore indicato in colonna 4 e la centrale cui è collegato il rilevatore indichi circa il valore indicato in colonna 5 Se il valore fosse diverso effettuare la Calibrazione Terminata la Verifica chiudere la bombola e togliere il TC011 Attendere 3 5 minuti per tornare alle condizioni di funzionamento normale 1 Modello 2 Gas da ...

Page 7: ...ave effects on the blood causing the formation of metaemoglobina In more severe cases it can lead to death Nitric ox ide is a pollutant that is generated in part in combustion processes in part by emissions from natural volcanic erup tions fires or civil activities and industrial processes involving combustion such as transport vehicles with diesel en gine gasoline LPG etc and the production of he...

Page 8: ...NITS In case of a central unit other then Tecnocontrol please verify the max load resistor as shown in Fig 4 The max load resistor is 50 ohm with 12Vdc power supply while is 400 ohm with 24Vdc power supply We suggest using 24Vdc power supply WARNING Average life In clean air and in normal working condition the sensor s life is about 2 years After this period the yellow Led FAULT flashes every 4 se...

Page 9: ...2 F1 this function allows completely recalibrate the sensor using the gas mixture indicated above Warning to guarantee that no errors of elaboration happen the possibility exists that during the Calibration the yel low Led switch off every 8 seconds in this case interrupt the procedure switch off and switch on the instrument and repeat the Calibration If condition persists it will be necessary to ...

Page 10: ...dans le l industrie du froid pour la production d explo sifs pour la production de plastiques et polymères et pour les solvants Le TS293EA H est comme le modèle précédente mais il utilise un capteur adapté pour les environnements pol lués et de l industrie et à la présence d autres gaz toxiques Le TS293EC S permet de détecter le Monoxyde de Carbone CO qui est un gaz toxique inodore sans couleur es...

Page 11: ...onnement Normal seule la led vert ON doit être allumée Alarme Le led rouge ALARM s allume si la concentration de gaz dépasse la valeur indiquée dans le tableau ci dessous selon le modèle Abilitation avec Dip Switch n 1 ON TS293EA TS293EA H TS293EC S TS293EC H TS293ES TS293EH TS293EHCN TS293EN TS293EN2 50 ppm NH3 200 ppm CO 10 ppm SO2 20 ppm H2S 5 ppm HCN 25 ppm NO 30 ppm NO2 Dérangement La central...

Page 12: ...93EHCN TS293EN TS293EN2 500 ppm NH3 1000 ppm CO 150 ppm SO2 500 ppm H2S 100 ppm EHN 1000 ppm NO 150 ppm NO2 Attention Les capteurs électrochimiques contiennent une petite quantité d acide sulfurique qui est corrosif Nor malement il ne doit y avoir aucune perte au capteur dans le cas contraire ceci est du à une action mécanique vio lente ou à un usage hors limites de fonctionnement Dans le cas d un...

Page 13: ... dique la valeur indique dans le tableau ci dessous dans la colonne 3 voir aussi Fig 3 Attendre 3 5 minutes envi ron puis quand la led rouge s allume et pendant qu elle est allumée appuyer sur la touche F2 et maintenir cette pression tant que la led rouge ne reste pas éteinte durant au moins 2 secondes si en revanche la led rouge conti nue à clignoter plus de 5 6 minutes cela signifie que le flux ...

Page 14: ...ido di azoto Nitrogen dioxide dioxyde d azote 20 ppm 2 2 1 Cloro Clorine Chlore 1 ppm 0 0 0 Etanolo Ethanol Éthanol 200 ppm 0 0 2 5 0 Etilene Ethylene Éthylène 100 ppm 0 0 80 50 Idrogeno Hydrogen Hydrogène 100 ppm 0 0 2 46 40 Idrogeno Solforato Hydrogen sulphide Sulfure d hydrogène 10 ppm 2 0 2 0 0 5 0 3 4 Monossido di carbonio Carbon Monoxide Monoxyde de carbone 100 ppm 0 1 100 100 1 Ossido di az...

Page 15: ...l Unit Centrale de détection RL S Dip Switch Test Uscita Output Test Sortie Test 40 200mV TP1 TP2 mV S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA Fig 2 Schema di collegamento Wiring diagram Schéma Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration 0 3 L min 1 L min Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resi...

Reviews: