background image

IST-293.IM01.01

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.5/10

 

 

 

 

TECNOCONTROL s.p.a:Via Miglioli 97 SEGRATE ( MI )ITALY 

Tel. +39 02 26922890 - Fax +39 02 2133734

 

 

communication or uncorrected) please replace with new one. 

3)

 

If a new

 

Cartridge Sensor

” is installed, or it is not 

correctly connected or a not compatible one is mounted. Please check the cartridge connections and compatibility 

(

see on page 1

) these checks are made connecting and disconnecting the device. If the condition does not change, 

please replace the unit and/or send it back to the supplier to repair. 

Yellow and green LED activates (

0mA output signal

):

 

this happens when the “

Cartridge Sensor

” is not working. First 

try to disconnect and connect the unit, finally try to replace a new 

Cartridge Sensor

”. If the condition is not change, 

please replace the unit and/or send it back to the supplier to repair. 

INSTALLATION 

The  gas  detector  must  be  accurately  installed  and  testing  according  to  the  national  dispositions  in  force  on  the 

safety of the plants and installation of electric devices in areas with danger of explosion. 

Mounting

: The 

Fig. 2

 shows the instrument size. The unit must be positioned vertically with the sensor downwards. 

Models TS293IM

 should be fixed at 20-30 cm from the ceiling (Methane is lighter than air). 

Model TS293IG 

should be fixed at 20-30 cm from the floor (LPG gas is heavier than air). 

Electrical Connection (

see Fig.2

)

: the maximum distance to install each detector from the Gas Central Unit is show 

in 

table 1

. Normally use a tree wire shielded cable. 

The terminals (

+ - S

), are polarized plug-in type, it is necessary to extract them to make the connection. 

Note:  Dip-Switch  should  be  set  with  instrument  powered  off.  Dip-Switch  1  settled  ON  activates  ALARM 

Red LED indication (see Table 2). 

Important

:

 after installing, 

power up the unit. 

It is not necessary perform any adjustment, 

wait about 20 to 30 min-

utes and then, 

if it is required

carry out the "

Operation Check

"

 

(

see ‘

Test and Calibration

). 

COMPATIBILITY WITH OTHER CENTRAL UNITS: 

In case of a central unit other then Tecnocontrol,

 

please verify 

the max load resistor as shown in 

Fig. 4

. We suggest using 24Vdc power supply. 

WARNING 

Average life

: The sensitive element used in this detector has an excellent stability in time. In fresh air and in nor-

mal working condition the sensor's life is about 5 years from the date of installation. After this period the yellow LED 

FAULT

” flashes every 3 seconds, is necessary replacing the “

Cartridge Sensor

”. 

Periodical  testing

: depending on the use, we advise to carry out working tests every 6÷12 months. Tests, Zero 

Adjust and Calibration with Gas/Air mixture as explained in chapter “

Tests and Calibration

”. 

Note:

 the detector is not able to detect gas leaks  occurring outside the room where it is installed, neither inside 

walls or under the floor. 

Warning:

 

Consider that in polluted environments, with the continued presence of vapours of flammable gases or 

over the standard temperature and pressure, the useful life of the sensor can be reduced. 

The NDIR sensor used in the models TS293 / IM and / IG is not able to detect Acetylene and Hydrogen. To detect 

acetylene must be required TS293IE model. 

TEST and CALIBRATION 

PAY ATTENTION

following tasks should be performed with attention and by competent and trained per-

sonnel; because starting this procedure it will cause the activation of connected alarm devices.

 

Operation Check, Zero Adjust and Calibration

:

 are different code protected functions. To access these functions 

is necessary to insert the relevant “

Code

" through the keys F1 and F2. To have the key pressure recognized, hold 

pressing it for around a second (

until the Green LED doesn't switch off for a moment

). Then the next key can be pressed. In 

case of error all it takes is waiting around 10 seconds and the sequence is automatically erased. 

Calibration Kit, Sample Gas Cylinders

 (

for Calibration Check and Calibration

) please, only use a mixture: 

MODEL 

Sample Gas Cylinder for Calibration 

Tecnocontrol Code 

TS293IM 

2.2% Volume 

(= 50% LEL)

  

Methane

 (CH

4

)

 

in air

 

Available on request

 

TS293IG 

0.7% Volume 

(= 50% LIE) 

 

Butane

 (C

4

H

10

)

 

in air 

Available on request

 

 

 

 

You  can  use 

disposable  cylinder,  complete  with  adjust  valve

.  Is  also  necessary  to  use 

the  calibration  kit 

Tecnocontrol model TC011

 (

for non-corrosive gases

) or 

TC014

 (

Stainless steel

).

 

“INSTRUMENT OPERATION CHECK” (

Check Code

: F2, F2, F1, F1)

this function allows to effect a functional test 

of the equipment. After having inserted the "

Check Code

", all LEDs are switched off. Then LEDs will switch on in se-

quence, from the yellow up to the red. At the end all the LEDs will remain lighted for around 5 seconds, and then 

the detector returns at the conditions of normal operation. It is advisable to perform this operation every 12 months 

according to the use. 

Note

: this function is not working if the red LED is already switched on. 

“ZERO ADJUST” (

Zero Code

: F2, F1, F1, F2)

this function is to adjust the Zero sensor and can be done in clean 

air only (environment without the presence of gas or other pollutants). Consider that the TS293I has a sophisticated 

follower of zero, that every hour will reset the sensor, if of course there is the presence of gas. If necessary, per-

form this operation after installation or after changing the “

Cartridge

” or every 6-12 months depending on environ-

mental conditions. After entering the "

Zero Code

" as confirmation of the operation, there will be a flashing red LED 

and output becomes 4.0 mA. 

Note

: This function is not working if mA output is more than 

5,6mA (10% LEL)

 and/or red or yellow LED is already 

been switched on. In this case, it will be necessary to recalibrate the unit and/or replacing the “

Cartridge

”. 

CALIBRATION” (

Calibration Code: F2, F2, F2, F1, F2, F2

):

 this function allows completely recalibrate the sensor using 

the gas mixture indicated above. 

Summary of Contents for TS293IG

Page 1: ... Limits Limite échelle 100 LIE LEL Vita media in aria Average Life in air Vie moyenne en air MTBF Sensore Sensor Capteur 5 anni years ans Tempo di risposta Response Time Temps de réponse T90 50 secondi seconds secondes Ripetibilità di zero Zero Repeatability Zéro répétitivité 1 LIE LEL Precisione Accuracy Précision 3 50 LIE LEL 5 50 LIE LEL Tempo di Preriscaldo Warm up time Temps de préchauffage 6...

Page 2: ...bilità del rilevatore nel tempo L unica causa di interferenza può essere data dalla pre senza di vapore acqueo che assorbe l infrarosso Nota i LED non sono visibili quando la custodia è chiusa Preriscaldo quando il rilevatore è alimentato inizia la fase di preriscaldo del sensore segnalata dal lampeggio del LED giallo FAULT Dopo circa 60 secondi il LED giallo si spegne e si accende quello verde ON...

Page 3: ...i effettuare un test funzionale del rilevatore Dopo aver inserito il Codice Test si spengono tutti i LED e si accenderanno in sequenza dal giallo al rosso L uscita 4 20mA rimane invariata Alla fine tutti i LED rimarranno accesi per circa 5 secondi poi il rilevatore tornerà nelle condizioni di funzionamento normale Si consiglia di eseguire quest operazione ogni 12 mesi in base all utilizzo Nota Non...

Page 4: ...calibrated to detect Methane a gas lighter than air Its density as to air is 0 55 and its LEL Lower Explosive Limit is 4 4 volume TS293IG LPG is calibrated to detect LPG Liquefied petroleum gas a gas heavier than air and consists of a mix ture of 20 30 Propane C3H8 and 80 70 Butane C4H10 Propane density as to air is 1 56 while Butane is 2 05 The LEL is 1 7 volume for Propane and 1 4 volume for But...

Page 5: ...walls or under the floor Warning Consider that in polluted environments with the continued presence of vapours of flammable gases or over the standard temperature and pressure the useful life of the sensor can be reduced The NDIR sensor used in the models TS293 IM and IG is not able to detect Acetylene and Hydrogen To detect acetylene must be required TS293IE model TEST and CALIBRATION PAY ATTENTI...

Page 6: ...ut value 0 5mA as indicated in column 7 The central unit should be display about the LEL value 3 as indicated in column 8 If the result is different is necessary to recalibrate the sensor see Calibration Then close the gas bottle remove TC011 or the TC014 Then the mA output will slowly decrease up to 4mA Example if you have to verify a TS293IG detector using a cylinder with Butane at 0 7 volume 50...

Page 7: ...e capteur Si les conditions persistent substituer et ou renvoyer la sonde au fournisseur pour réparation INSTALLATION Les détecteurs doivent être installés positionnés et vérifiés en suivant toutes les règles nationales en vigueur pour les installations électriques dans les zones avec dangers d explosions et les normes de sûreté des installations Montage en Fig 1 sont indiquées les dimensions La s...

Page 8: ...r la Cartouche Capteur ETALONNAGE Code de Etalonnage F2 F2 F2 F1 F2 F1 cette fonction permet l étalonnage du capteur avec le mélange de gaz prévu Durant la procédure il existe la rare possibilité que la led jaune s éteigne chaque 8 secondes le système ne réus si pas à lire les données de la Cartouche capteur dans ce cas interrompre la procédure couper puis rétablir l alimentation de la sonde Refai...

Page 9: ... 24Vcc The maximum distance to install each detector from the 24Vdc power Supply Distance maxi d installation du détecteur sous 24Vcc 0 75 mm 2 26 Ω km 100 m 300 m 1 mm2 20 Ω km 150 m 400 m 1 5 mm2 14 Ω km 200 m 500 m 2 5 mm 2 8 Ω km 400 m 800 m Tabella 2 Table 2 Tableau 2 S1 SET Dip Switch LED Allarme 1 2 3 4 Alarm LED LED d alarme ON ON ON ON OFF ON OFF OFF OFF ON Tabella 3 Table 3 Tableau 3 1 2...

Page 10: ... Output Test Sortie Test 40 200mV TP1 TP2 S Uscita 4 20 mA 4 20 mA Output Sortie en 4 20 mA Fig 2 Schema di collegamento Wiring diagram Schéma F2 F1 mV TEST mV Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration TC011 o or ou TC014 Bombola di gas titolato Sample gas cylinder Bouteille de gaz titré 0 3 0 5 L min 1 L min Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 2...

Reviews: