TFA2-596 - TFA4-1192
12
Synoptic repeater
The synoptic repeater panel performs the same functions as the repeater and, in addition, it manages dynamically or on request
up to 32
fl
oor plans with up to 32 interactive icons each.
Additional power supply
The system provides for the use of additional power supplies, which allow to increase the power supply and autonomy of the system.
The power supplies can be freely distributed within the infrastructure of the loop. The Tecno
fi
re power supplies are constantly supervised
by the control panel and comply with the applicable standard EN 54-4-A2:2006.
Zones
Each zone may control 1 to 32 detection and/or actuation devices, typically detectors and modules (maximum number of devices de
fi
ned
by EN 54). The control panel controls up to 150 zones, which can be specialized as
fi
re zones or technical zones.
Virtual zones
The control panel can manage up to 100 virtual zones. The virtual zone is an abstract set which includes detection and/or actuation devices,
typically detectors and modules. The virtual zones do not cause any kind of alarm noti
fi
cation, but can be recalled as operands within formulas.
The virtual zone may consist of devices, belonging to different loops and even to other virtual zones.
Formulas
The formulas determine the rules of behavior affecting the operation of the devices, on the basis of the dynamic behavior of the system.
Alarm plans
Each
fi
re or technical zone can be associated with a speci
fi
c alarm plan that, in the event of an alarm, is viewed by the control panel
and the repeaters of the system.
The alarm plan informs the operators about the behavior and the measures to be taken to deal with the alarm in the speci
fi
c zone.
Programmable outputs
In addition to the mandatory alarm, failure and reset outputs, the control panel features 2 programmable outputs. For each of them it is possible
to program a function and the logic status (standard or reversed).
Access periods
The control panel manages 8 access periods that can be recalled as operands within formulas governing the operation of the output modules,
sirens and optical-acoustic alarm devices.
The access periods invoked within a formula perform the operation requested by the associated operand.
The access periods can also be used to enable the monitored system mode.
Customizable calendar
The control panel is equipped with a customizable four-year calendar that manages all the operations controlled by the clock.
It is possible to de
fi
ne weekdays, holiday eves, holidays and automatic Daylight Saving Time setting.
Personal computer interface
The control panel has an USB interface dedicated to the connection of a personal computer with which it is possible to perform, depending
on the access level, all programming operations and the system
fi
rmware update.
Serial printer interface
The control panel provides a TTL port dedicated to connecting a PROG32 interface to which you can connect a serial printer.
Event buffer
The control panel stores in its non-volatile buffer up to 8192 events in descending chronological order.
The memory contents can be displayed via the control panel or sent to the printer through the TTL port. Events can be displayed and
fi
ltered
by the software. For this, the events are downloaded and saved in a log
fi
le on the software.
Communication analysis
The control panel constantly supervises all communications among the devices that make up the system and registers possible errors.
Summary of Contents for Tecnofire TFA2-596
Page 2: ...TFA2 596 TFA4 1192 2...
Page 4: ...TFA2 596 TFA4 1192 4...
Page 10: ...TFA2 596 TFA4 1192 10...
Page 14: ...TFA2 596 TFA4 1192 14...
Page 28: ...TFA2 596 TFA4 1192 28...
Page 32: ...TFA2 596 TFA4 1192 32...
Page 40: ...TFA2 596 TFA4 1192 40...
Page 50: ...TFA2 596 TFA4 1192 50...
Page 62: ...TFA2 596 TFA4 1192 62 NOTES...
Page 63: ......