TFA2-596 - TFA4-1192
13
TFA2-596 • TFA4-1192 -
Technical and functional specifi cations
Detectors
Modules
Zones
Total connectable detectors
796 (TFA4-1192)
398 (TFA2-596)
Total detectors per loop
199
Total connectable modules
396 (TFA4-1192)
198 (TFA2-596)
Total modules per loop
99
Total zones
300
Virtual zones
100
CPU
outputs
Hard-programmed relays
2
Programmable relays
3
Programmable open-collectors
3
Controlled siren output
1
Reset output
1
System
features
True color TFT display
480 x 272 pixel
Voice synthesis
Customizable
vocabulary
Detection loops
4 (TFA4-1192)
2 (TFA2-596)
RS485 serial buses
Master Bus (1 port)
Slave Bus (1 port)
Event buffer capacity
8192
Access
management
Access levels
4
Access codes
10
Monitored system mode
✓
Protocols
Loop
Fire-Speed
RS485 serial bus
Fire-Bus
Ethernet hub
Type
Standard 803.2
Connection channels
Local Server
Remote Server
Tecnoserver
Call back
Notifi cation channels
8
IP addresses
16 (2 per channel)
Transmittable events
15 categories
Protocols
5 IP protocols
Encryption
AES 128 bit
Transmission time
SIA IP DC-09 10s
Call event queue
64 events
Automation
Formulas
400 (TFA4-1192)
200 (TFA2-596)
Alarm plans
200 (TFA4-1192)
100 (TFA2-596)
Access periods
32
Calendar
Quadrennial
(programmable)
Test call with TCP/IP
✓
Expandability
Serial expansions (max. 16)
TFT-7
TFT-7S
Telephone
communicator
Ethernet interface
Network confi guration
1 15 slaves
Serial printer
✓
Electrical
specifi cations
CPU
CPU board consumption
200mA @ 24V DC
Electrical outputs
I max. 50mA
Power supply voltage
(loop, serial bus, sirens)
20V…27.6V DC
Modular
power supply
Type
A - switching
Fly-back
Operating voltage
230V AC +10%
-15% 50Hz
Power supply consumption
700mA AC
Rated output current
5A @ 27.6V DC
Max. current available
5A
Peak-to-peak ripple voltage
≤150mV p-p
Battery protection fuse
T 1.6A
Battery
Capacity
2x 12Ah/12V
Flame class
V-2 or superior
Cut-off voltage
<17.6V DC
Recharge time
100% in 24h
Physical
specifi catons
Environmental class
3K5
(EN 60721-3-3:1995)
Operating temperature
-5°C...+40°C
Relative humidity
(without condensation)
10%...93%
Protection class
IP30
Casing
Aluminium - Steel
Dimensions (L x H x D)
441 x 347 x 149mm
Weight (without batteries)
6.2kg
Conformity
Fire alarm panel
EN 54-2:1997 +
A1:2006
Power supply
EN 54-4:1997 +
A2:2006
Certifi cation number
0051-CPR-0388
(TFA4-1192)
0051-CPR-0389
(TFA2-596)
Year of CE marking
14
Number of declaration of
performance
002_TFA4-1192
(TFA4-1192)
003_TFA2-596
(TFA2-596)
Notifi ed body
IMQ
Summary of Contents for Tecnofire TFA2-596
Page 2: ...TFA2 596 TFA4 1192 2...
Page 4: ...TFA2 596 TFA4 1192 4...
Page 10: ...TFA2 596 TFA4 1192 10...
Page 14: ...TFA2 596 TFA4 1192 14...
Page 28: ...TFA2 596 TFA4 1192 28...
Page 32: ...TFA2 596 TFA4 1192 32...
Page 40: ...TFA2 596 TFA4 1192 40...
Page 50: ...TFA2 596 TFA4 1192 50...
Page 62: ...TFA2 596 TFA4 1192 62 NOTES...
Page 63: ......