TFA2-596 - TFA4-1192
44
C
ALL
NC NA
C
OUT1
NC NA C
OUT2
NC NA
C
FAULT
NC NA
C
OUT3
RESET
NC
NC
NA NA
-
-
-
OUT4
OUT5
OUT6
-
+
-
+
-
+
-
+
-
+
B
A
TFA4-1192
JP1 BATT
F1 5A - F
RJ45
9-3 - TFA4-1192 terminals
CPU board
connector
Ethernet
connector
Battery
connection
Power supply
connector
PROTECTION AGAINST DEEP DISCHARGE
JP1 BATT
Automatic battery release due to low battery voltage for Vbat <18V DC
The battery automatic release function is disabled
Warning:
the outputs OUT1 (terminals 7, 8, 9), OUT2 (terminals 10, 11, 12), OUT3 (terminals 13, 14, 15),OUT4 (terminal 20),
OUT5 (terminal 21), OUT6 (terminal 22), alarm relay otput ALL (terminals 1, 2, 3) and the relay output RESET (terminals 16, 17)
are not supervised (type C, E, J according to EN 54-1 nomenclature). Therefore, in accordance with EN 54-2, they may not be
used to control
fi
re alarm devices or transmission devices for
fi
re or failure alarm.
The failure relay output FAULT (terminals 4, 5, 6) is not supervised (type J according to EN 54-1 nomenclature) and therefore,
in accordance with EN 54-2, may not be used to control transmission devices for failure alarm.
Fuse F1
Battery polarity reversal safety fuse (type 5A - F 5x20)
Summary of Contents for Tecnofire TFA2-596
Page 2: ...TFA2 596 TFA4 1192 2...
Page 4: ...TFA2 596 TFA4 1192 4...
Page 10: ...TFA2 596 TFA4 1192 10...
Page 14: ...TFA2 596 TFA4 1192 14...
Page 28: ...TFA2 596 TFA4 1192 28...
Page 32: ...TFA2 596 TFA4 1192 32...
Page 40: ...TFA2 596 TFA4 1192 40...
Page 50: ...TFA2 596 TFA4 1192 50...
Page 62: ...TFA2 596 TFA4 1192 62 NOTES...
Page 63: ......