INSTALLATION AND SETTING INSTRUCTIONS
7
28.
0
CONNECTION
The electric and hydraulic connection is to be carried out in compliance with all the relevant Regulations and
they should not be a hinder to the machine.
SAFETY FLOW GAUGE
To guarantee a correct machine operation it is required to install on the plant a device (e.g. air gauge)
breaking burner operation in the event that air flow decreases beyond the minimum value set forth in
section SPECIFIC TECHNICAL DATA.
29.
0
TREATED AIR SUCTION – OUTLET DIRECTION
IN
Direction – suction direction of air to be treated
OUT
Direction – suction direction of treated air
30.
0
ORIGINAL ACCESSORIES
To install the accessories, follow the instructions included in the relevant package.
37.
0
CONDENSATION CHECK
The appliance is designed to be operated with the heating capacity and the air flow rate specified in the
Data Sheet chapter. If the heating capacity is too low and/or the air flow rate is too high, combustion
products may condensate, resulting in the irreparable corrosion of the heat exchanger. If the heating
capacity is too high and/or the air flow rate is too low, an anomalous overheating of the heat exchanger
may occur, resulting in the activation of the safety devices and causing damage to the exchanger.
It has to be checked if condensation is forming inside the heat exchanger during its
functioning. This check should be performed by turning off the burner after half an hour
of continuous functioning, checking if there is any trace of humidity in the exhaust
manifold.