GB / IE - 2
5410.263.00
When checking for leaks do not use naked flames!
The manufacturer shall not be held responsible and the guarantee is void in the case of damage caused by negligence in
following the operating and installation instructions or by improper use. The guarantee is void in the case of connections which
have been made in a way which doesn't meet the current standards and fire-fighting regulations.
Evacuation of unburnt gases
This equipment doesn't need to be connected to a flue (A1type of construction), but we do recommend installing it under an extractor hood.
Checking the pressure
The distribution network pressure must meet the following
specifications:
ALLOWED
From 20/25 to 35/45 mbar
LPG
NOT ALLOWED
Below 20/25 above 35/40 mbar
ALLOWED
From 17 to 25 mbar
METHANE
H
NOT ALLOWED
Below 17 above 25 mbar
If the gas distribution network pressure on the installation site doesn't
meet the above values, inform the gas board and do not turn the unit
on until the cause and a solution have been found.
The distribution network pressure can be taken with a U manometer
(min. definition 0.1 mbar), connected to the pressure outlet behind
control panel “H” (fig.5).
1.
Remove the control panel.
2.
Remove screw "Y" and the sealing washer (fig.5) from the
pressure outlet and connect the manometer.
3.
Turn the appliance on following the enclosed instructions and
check that the pressure is within the permitted pressure range.
4.
Disconnect the manometer and replace screw "Y" and the
sealing washer (fig.5) in the pressure outlet.
5.
Remove the control panel.