USER PARAMETER SETTINGS
Parameter
Min.
Max. Unit/meas. DEF
PA PASSWORD
-99
+99
Number
-19
/ = PROBE PARAMETERS
/1 Cell probe calibration
-10
+10
°C
0
/2 Evaporate probe calibration
-10
+10
°C
0
/3 Core probe calibration
-10
+10
°C
0
/8 Temperature scale (0=Fahrenheit 1=Celsius)
0
1
Flag
1
c = CHILLING / FREEZING
c0 Cell probe differential
1
15
°C
+3
c1 Duration of timed chilling and max. duration for chilling by temperature
0
400
min
90
c2 Chilling end set point (core probe)
-55
+99
°C
3
c3 Positive storage set point (cell probe)
-55
+99
°C
2
c4 Duration of timed freezing and max. duration of freezing by temperature
(when c4=0, key and freezing function to -18°C are disabled.
For chilling units only.)
0
400
min
240
c5 Freezing end set point (core probe)
-55
+99
°C
-18
c6 Negative storage set point (cell probe)
-55
+99
°C
-25
c8 Positive and negative chilling duration countdown start temperature
-55
+99
°C
+65
cA Core probe readout (readout only)
---
---
°C
---
cb Set point for SOFT blast chilling (cell probe) and during second stage
of HARD blast chilling
-55
+99
°C
-5
cd HARD chilling set point (temperature transition HARD ->SOFT of core probe)
-55
+99
°C 2
0
cF Cell set point during first stage of HARD blast chilling (core probe)
-55
+99
°C
-20
d = DEFROST
d0 Defrosting interval (0 = no defrost)
0
99
hours
8 h
dA Defrost probe readout (readout only)
---
---
°C
---
U = VARIOUS
u5 Duration of UV lamp activation (if u5=0, UV key is disabled)
0
99
min
0
uA Print interval (when uA=0, HACCP key is disabled)
0
99
min
20