User’s manual 

2

 

UPS ERA PLUS 900-1.100 

 

Safety Warnings 

 

                                                                        

 

 

Read  this  manual  carefully  and  completely  before  installing  and  using  the  TECNOWARE  ERA 
PLUS Uninterruptible Power Supply, which, from here after, will also be referred to as UPS. 

 

This manual should be kept close to the UPS and read before the UPS is installed and used. 

 

The  UPS  must  be  used  only  by  properly  trained  personnel.  To  ensure  correct  and  safe 
operations,  it  is  necessary  that  operators  and  maintenance  personnel  observe  the  general 
safety Standards as well as the specific instructions included in this manual. 

 

Risk of electric shock: do not remove the cover. The UPS contains internal parts, which are at a 
high  Voltage  and  are  potentially  dangerous,  capable  of  causing  injury  or  death  by  electric 
shock. 

 

There are no internal parts in the UPS, which are user serviceable. Any repair or maintenance 
work  must  be  performed  exclusively  by  qualified  technical  personnel  authorized  by 
TECNOWARE. TECNOWARE declines any responsibility if this warning is disregarded. 

 

Warning  to  the  technical  personnel  authorized  for  Service:  since  internal  components  are 
connected to the batteries, they will remain powered, and therefore dangerous, even after the 
UPS  has  been  disconnected  from  AC  power  mains.  Before  any  repair  or  maintenance  work, 
disconnect the batteries, by removing the positive cable (red colour) from the positive pole of 
the battery.  

 

It is compulsory to ground the UPS according to Safety Standards. The AC mains power supply 
socket used to power the UPS must have an earth connection. 

 

In  the  event  of  AC  main  power  supply  failure  (when  the  UPS  works  in  Battery  mode),  do  not 
unplug the power supply cable to the UPS to ensure earth continuity to the connected loads. 

 

Since the AC mains power supply cable acts as a separation device, the AC mains power socket 
used to supply the UPS and/or the rear side of the UPS must be accessible to easily disconnect 
the cable in case of dangerous conditions. 

 

Risk of electric shock at the Output lines when the UPS is ON. 

 

Risk of electric shock at the Output lines while the unit is connected to the AC utility line. 

 

Do not obstruct ventilation slots or holes and do not rest any object on top of the UPS. 

 

Do not insert objects or pour liquids in the ventilation holes. 

 

Install the UPS indoors, in a protected, clean and moisture-free environment. 

 

Do not expose to the direct sun light. 

 

Do not keep liquids, flammable gases or corrosive substances near the UPS.  

                                                                        

 

 

 

Summary of Contents for ERA PLUS 1.100

Page 1: ...Uninterruptible Power Supply ERA PLUS 900 ERA PLUS 1 100 User s manual...

Page 2: ......

Page 3: ...9 9 Maintenance 11 9 1 UPS Cleaning 11 9 2 Battery 11 9 3 Battery Replacement 11 9 4 Operator Safety 12 10 Troubleshooting 12 Conformity to the European Directives 14 Product Disposal 14 Lead Batteri...

Page 4: ...he batteries they will remain powered and therefore dangerous even after the UPS has been disconnected from AC power mains Before any repair or maintenance work disconnect the batteries by removing th...

Page 5: ...ure or a low battery condition directly to a computer this makes it possible to automatically save your data during an extended black out with the most widespread operating systems Windows Mac OS X Li...

Page 6: ...ackaging and carry out a meticulous inspection We recommend keeping the original packaging in a secure place in case you need to send the UPS for maintenance purposes In case of transport damage notif...

Page 7: ...d measurements Front panel shown below consists of two parts 1 The ON OFF button enables the user to turn ON OFF the UPS 2 The LINE BATTERY led this led blue color is always on during the functioning...

Page 8: ...50 V 3 Grounded UPS Output receptacles Schuko Italian type black colour to supply critical loads 4 Computer Interface USB connector it is the communication USB port Only for UPS ERA Plus 1 100 In case...

Page 9: ...g correctly 7 Simulate a black out by removing the AC Input line The UPS starts working in Battery mode the UPS emits a brief acoustic signal every 10 seconds 8 Be sure that all the devices connected...

Page 10: ...seconds and simultaneously the LINE BATTERY led flashes 6 3 Low Battery and Automatic Restart In Battery mode ERA PLUS indicates the Low Battery condition whenever the battery reaches a charge level...

Page 11: ...chapter Technical Characteristics as this may damage the unit In this case the warranty is void 6 5 Fault Condition The UPS indicates the Fault condition by emitting a continuous acoustic alarm During...

Page 12: ...ve CEI EN 62040 2 2006 EMC Directive Battery Type Lead acid sealed free maintenance Number of batteries 1 Nominal Battery Voltage 12 Vdc Battery Specifications 12 Vdc 4 5 Ah 6 cells 12 Vdc 7 2 Ah 6 ce...

Page 13: ...Take in mind that batteries are recharged automatically if the UPS works in Normal mode or if the UPS is off and connected to the AC Input Line Battery life strongly depends on the ambient temperatur...

Page 14: ...afety Whenever the UPS is not responding anymore to original characteristics the UPS must be made non operative and every usage not authorised must be avoided After it will be necessary to refer to qu...

Page 15: ...cal mains Input mains fuse is burnt Replace the fuse with another of the same type Black out conditions surge Over Voltage or Low Voltage Wait until the AC Input Line returns to normal conditions Elec...

Page 16: ...rban waste but must be treated as a separate waste Any violation is indictable with financial sanctions as per in force regulations An incorrect waste disposal or an improper use of the same or of any...

Page 17: ......

Page 18: ......

Page 19: ...TECNOWARE s r l www tecnoware com...

Reviews: