User’s Manual
8
UPS EVO DSP TT
2.5.1 Internal Battery Connection
The models EVO DSP TM 10-30 KVA can be equipped with internal batteries. In such case
these devices may have very hazardous voltages on the Battery terminals.
When the UPS has battery inside, before doing any operation please do the following
points:
1. Remove the back UPS cover to access to the battery pack.
2. Connect the positive battery terminal A see the following figure).
3. Connect the positive battery terminal B (see the following figure).
4. Connect the positive battery terminal C (see the following figure).
5. Replace the back UPS cover.
PAY ATTENTION: RISK OF ELECTRICAL SHOCK – HIGH BATTERY VOLTAGE
A, B and C battery terminals are disconnected in factory to reduce the risk of electrical
shock during shipment. After points 2, 3 and 4 the NOMINAL TOTAL BATTERY VOLTAGE is
about 744 VDC (there are 62 batteries 12 VDC serial connected).
Figure – A, B and C Battery terminals connections
A
B
C
Summary of Contents for EVO DSP TM
Page 1: ...Uninterruptible Power Supply EVO DSP TM 10 30kVA User s manual ...
Page 2: ......
Page 42: ......
Page 43: ......