User’s Manual
18
UPS EVO DSP TT
“MEASUREMENTS” MENU
MEASUREMENT
DEFINITION
LD
= XXX
%
Ratio of the actual Inverter active power to its nominal value.
Vsc
= XXX
V
Output line/neutral voltage.
Isc
= XXX
A
Output line current.
Fo
= XX.X
Hz
Frequency of output Line/Neutral voltage.
Vby
= XXX
V
Bypass Line/Neutral voltage.
Vin
= XXX,XXX,XXX
V
Input Line/Neutral voltages.
Iin
= XXX,XXX,XXX
A
Input currents.
Fin
= XX.X
Hz
Frequency of input Line/Neutral voltages.
Vdc
= XXX,XXX
V
Positive and negative DC bus voltages.
Vbat = XXX,XXX
V
Positive and negative battery branch voltages.
Ibat
= ±XXX,±XXX
A
Positive and negative battery branch currents.
Positive during charge, negative during discharge.
Tbat = XXX
°C
Ambient temperature.
“COMMANDS” MENU
PRIORITY
= INVRTR/BYPASS
Selects the priority for Normal mode or Bypass mode.
Push ENTER to switch between INVRTR and BYPASS.
START B. TEST
Push ENTER to start the Battery Test.
BUZZER
= ENBLD/DSBLD
Enable or disable the buzzer.
Push ENTER to switch between ENBLD and DSBLD.
COMM
= RS232/RS485
Push ENTER to switch between RS232/RS485 communication.
EXTENDED
CMNDS
Push ENTER to enter this submenu.
“EXTENDED CMNDS” SUBMENU
RECTFR
= ENBLD/DSBLD
Enable or disable operation of the Rectifier block.
Push ENTER to switch between ENBLD and DSBLD.
= BLCKD
Can be seen only when the Rectifier is blocked.
Push ENTER to remove the blockage and enable the Rectifier.
INVRTR
= ENBLD/DSBLD
Enable or disable the operation of the Inverter block.
Push ENTER to switch between ENBLD and DSBLD.
= BLCKD
Can be seen only when the Inverter is blocked.
Push ENTER to remove the blockage and enable the Inverter.
BYPASS
= ENBLD/DSBLD
Enable or disable the operation of the Bypass thyristors.
Push ENTER to switch between ENBLD and DSBLD.