11 EMERGENCY POWER OFF
Partial shutdown: results in deactivating the static and the inverter, which in consequence will turn off all the electric
equipment connected to the system’s output, whereas the rectifier and battery will continue receiving charge current.
Total shutdown deactivates all functions (including the rectifier). During the emergency the message “warning
emergency shutdown” will appear on the control panel.
CAUTION!:
THE FOLLOWING PROCEDURE WILL DISCONNECT THE LOAD
EPO (Emergency power off) is used to turn off rectifier, inverter and static bypass as soon as epo contact is close.
Load is not supplied. EPO is useful in emergency situations (for example fire) to disconnect load from supply line.
11.1 EPO TYPE
11.1.1 EPO ON CONTROL PANEL
If EPO is installed on machine, it is always visibile on control panel.
11.1.2 EPO ON REMOTE PANEL
If EPO is installed on remote panel, it is always visible on this. So it is possible to force epo from the remote place.
11.2 PROGRAM EPO
By control panel is possible to program the behaviour of EPO.
Insert J1 on A11
Press F6+F3 keys and enter menu
By F7, F8 keys select EPO and press F6 to confirm
By F7,F8 keys select behaviour type
Is possible to select between three modes:
Not active
Partial shutdown
Total shutdown
Esc to program menu and remove J1 to A11
11.3 RECOVERY FROM EPO
Press epo button and then press start green button on control panel