EV Inverter Operating Manual
___________________________________________________________________________
TECO
– Westinghouse Motor Company 17
Section 10
-
Parameters F (Basic) and C (Advanced) Function Tables
Overview
– The
EV
Inverter Series is program capable to allow for a variety of application
requirements. The parameters are split into two categories,
F
and
C.
The
F
parameters set the
Basic
functions of the inverter while the
C
parameters control the more
Advanced
functions.
The parameters can be accessed and changed through the keypad. (Refer to Sec.9 for keypad
functions and navigation). They may also be accessed and changed though
MODBUS
protocol in
conjunction with an optional communications module (Refer to
Sec. 2
for available
communication options).
When the inverter is shipped from the factory each parameter is set at a
Factory Default
value
and is so specified in the Tables. Most parameters
may not
be changed when the inverter is in
the
RUN
mode. Those parameters that can be are so noted (note 1) in the
Remarks
column.
Table 10.1
F (Basic) Parameters
F
Parameter
Code
Range/ Function
Factory
Default
Remarks
F00
Inverter horsepower capacity
code
-
Note 5
F01
Acceleration time 1 (
sec.
)
-
00.1
– 999
05.0
Note 1 & 2
F02
Deceleration time 1 (
sec.
)
-
00.1
– 999
05.0
Note 1 & 2
F03
Motor rotation direction
000 Forward
000
Note 1
001 Reverse
F04
Run command source
000 Keypad
000
001 External terminal
002 Communication control
F05
Frequency command
source
000 UP/Down key on keypad
000
001 Potentiometer on keypad
002 AIN (input signal from TM2)
003
Multi-function input terminal
UP/DOWN function
004
RS-485 Communication
frequency setting
F06
External control operation
mode
000
Forward / Stop -
Reverse / Stop
000
001
Run / Stop-
Forward / Reverse
002 3-wire
—Run / Stop
F07
Frequency upper limit (
Hz
)
-
01.0 - 200
50.0 / 60.0
Note 2 & 7
F08
Frequency lower limit (
Hz
)
-
00.0 - 200
00.0
Note 2