F09
Stopping method
000 Decelerate to stop
000
001 Coast to stop
F10
Status display parameters
000 Disable
000
Note 1
001 Enable
F11
F12
F13
F14
F15
Terminal S1 function
Terminal S2 function
Terminal S3 function
Terminal S4 function
AIN
–
Can be set as an
analog input (017 Factory
default or 018) or as a digital
input and becomes S7
Note:
Digital inputs S1
– S4, *S5 and
S6 and S7 can be
programmed with Codes 000
–
016 and 019 only. Codes 017
and 018 are reserved for when
AIN is used as an analog input
*Digital Inputs
S5 & S6
are
provided by an optional I/O
Module SIF-IO. ( see Sec.,
Fig. 2.6)
000 Forward
S1 = 000
S2 = 001
S3 = 005
S4 = 006
AIN = 017
001 Reverse
002 Preset speed command 1
003 Preset speed command 2
004 Preset speed command 3
005 Jog frequency command
006 Emergency stop (E.S.)
007 Base block (b.b.)
008
Select 2
nd
acceleration /
deceleration time
009 Reset
010 Up command
011 Down command
012 Control signal switch
013 Communication control
signal switch
014
Acceleration / deceleration
prohibit
015
Master / Auxiliary speed
source select
016 PID function disable
017
Analog signal input
(terminal
AIN
)
018
PID feedback signal
(terminal
AIN
)
019 DC Injection brake signal
*F16
AIN signal select
000 0-10V (0-20mA)
000
001 2-10V( 4-20mA)
*F17
AIN gain (%)
-
000
– 200
100
Note 1
*F18
AIN bias (%)
-
000
– 100
000
*F19
AIN bias
000 Positive
000
001 Negative
*F20
AIN slope direction
000 Positive
000
001 Negative
*
Parameters F16