EV Inverter Operating Manual
___________________________________________________________________________
TECO
– Westinghouse Motor Company 50
C41 Local /Remote control select description
•
Local mode
Run command:
The Run / Stop button on the keypad controls drive operation. Parameter F04 setting has no
effect on control.
Frequency command:
When C41=000, the Up / Down key on the keypad controls the inverter and the F05
setting has no effect.
When C41=001, the potentiometer on the keypad controls frequency, and the F05 setting
has no effect.
•
Remote mode
Run command:
The Run command is set by the value of F04.
Frequency command:
The frequency command is set by the value of F05.
•
The control mode is changed by simultaneously pressing V/RESET and DATA/ENT keys.
NOTE:
The Inverter must be in STOP mode
Refer to Parameters F11 - F14 for a detailed explanation
1.) As an example, if the C44 scan time is set to 80 ms (i.e N=10), then any digital input signals
applied for less than 80 msec will be ignored.
2.) If the scanned signal is seen for N times (scan times), the inverter responds to it as a
signal change.
If it is seen for less than N times, it is considered noise. Minimum Scan time = 8ms.
3.) The user can set scan interval times according to the noise in the operating environment. Extend
the values of C44/C45 if noise is a problem, however this will reduce the signal response time.
C42/43
(SIF-IO option card)
S5 / S6 terminal on MFIT Setting
000: Forward
001: Reverse
002: Preset speed command 1
003: Preset speed command 2
004: Preset speed command 3
005: Jog frequency command
006: Emergency stop (E.S.)
007: Base block (b.b.)
008: Switch to 2
nd
acceleration/ deceleration time.
009: Reset
010: Up command
011: Down command
012: Control signal switch
013: Communication control signal switch
014: Acceleration / deceleration disable
015: Master / Auxiliary speed switch
016: PID Function disable
019: DC Injection brake signal
C44: Multi-function input terminal S1-S6 signal scan time (N msec ×8), N = (1 - 100 times)
C45: AIN signal scan time (N msec ×8), N = (1 - 100 times)