EV Inverter Operating Manual
___________________________________________________________________________
TECO
– Westinghouse Motor Company 52
C50 Baud rate (bps)
0 0 0 : 4 8 0 0
0 0 1 : 9 6 0 0
0 0 2 : 1 9 2 0 0
0 0 3 : 3 8 4 0 0
C51 Stop bit
000: 1 Stop bit
001: 2 Stop bit
C52 Parity bit
000: No parity
001: Even parity
002: Odd parity
C53 Data bits
000: 8 Bits data
001: 7 Bits data
1.) RS-485 communication:
(requires RS485 option SIF-485)
1 to 1 control: A PC or PLC controls one inverter (C49 communication address to 001 - 254).
1 to multiple inverters control: A PC or PLC controls several inverters (up to 254) inverters use
parameter C49 to set the communication address (001 - 254). When the communication address
=000, the inverter is controlled by serial communication regardless of the C49 setting.
2.) RS-232communication:
(requires RS232 option SIF-232)
1 to 1 control: A PC or PLC controls one inverter (C49 communication address to 001 - 254).
NOTES: a
.The BAUD RATE (C50) and communication format (C51/C52/C53) of the Host Computer
or PLC and inverter must be the same.
b
. The inverter will validate the modified parameters after the parameters are modified by
the Host Computer or PLC.
c
. Communication protocol:
refer to the EV MODBUS communication protocol manual
d
. Parameters C49 - C53 cannot be changed via the communication module
C54/ C55 Communication error detection time / Communication error operation selection
1.) Time out detection time: 00.0 - 25.5sec; setting 00.0 sec, disables the time out function.
Default: 00.0sec *
Cannot be modified when in serial communication mode
.
2.) Time out operation selection:
000: Deceleration to stop (F02: Deceleration time 1).
001: Free run (coast) to stop.
002: Deceleration to stop (C12: Deceleration time 2).
003: Continue operating.
Default=000 *
Cannot be modified when in serial communication mode
.