3-62
(32)
Multi-Function Analog Input Function Selection (Sn-29)
•
The settings and functions for the multi-function analog input (terminal AUX) are
listed in Table 15.
Table 15
Multi-function analog input function list
Setting
Function
LCD Display
Description (100% output corresponds to 10 V level)
00
Auxiliary frequency
command
Auxilary Freq.Cmd. (Max. output frequency)
01
Frequency command
gain (FGAIN)
Instruction gain 1
Total gain
=
(Bn-05, Bn-07) ×FGAIN
02
Frequency command bias
1 (FBIAS1)
Cmd. Bias 1
Total bias
=
(Bn-06, Bn-08) + FBIAS1
03
Frequency command bias
2 (FBIAS2)
Cmd. Bias 2
Total bias
=
(Bn-06, Bn-08) + FBIAS2
04
Torque detection level 1
Tq. Detect Level 1 According to analog input voltage (0
~
10V), change
torque detection 1 level (setting of Cn-32 is disabled)
04
Overtorque detection
level
Over Tq. Level
According to analog input voltage (0
~
10V), change
overtorque detection level (setting of Cn-32 is
disabled)
05
Output frequency bias
(VBIAS)
Output Voltage
Total output voltage= V/F pattern v VBIAS
06
Scaling of ACC/DEC
time(TK)
Acc&Dec Coeff
Real ACC/DEC time= ACC/DEC time (Bn-0~24) / TK
07
DC injection braking
DC Brakin current
According to analog input voltage (0
~
10V), change
the level of DC injection current (0-100
%
).
(inverter rated current=100%, the setting of DC
injection current Cn-15 is disabled )
08
Stall prevention level
during running
Run Still Level
According to analog input voltage (1.5V
~
10V),
change the level of stall prevention during running
(30%
~
200%)
(inverter rated current=100%, the setting Cn-26 is
disabled.)
09
PID control reference
input
PID Command
Multi-function analog input (terminal AUX) used as PID
control reference input (0~10V). Please refer to “PID
CONTROL BLOCK DIAGRAM” on page
3-7
.
10
Frequency command
lower limit
Freq. Cmd. Low
Bound
Change the frequency command lower-limit (0-100
%
)
value according to the then analog input voltage
(0~10V)
(Max. output frequency (Cn-02) corresponds to the
100% analog output. The actual lower-limit is
determined by the maximum of Cn-19 and the value
corresponding to the multi-function analog input
terminal).
11
Jump frequency setting4
Freq Jump 4
Set the jump frequency 4, according to analog input
voltage (0~10V), while Cn-20~Cn-23 can be used to
set the jump frequency 1~3 and their jump frequency
width.