App-4
C. Wiring for PG Feedback Use
The MA7200 inverter has a built-in PG interface, no external PG feedback option
card is needed. An independent DC source of +12V should be provided from an
external source.
IP12
AC 200~240V
50/60Hz
IP12
MA7200
P
Encoder
+12V
0V
1
2
3
4
Power Supply
(L)
(N)
FG
U/T1
V/T2
W/T3
TP1
R/L1
S/L2
T/L3
IM
PG
OPEN
PULL UP
IG12
E
A(+)
A(-)
E
P
P
Fig. 49.
Wiring of PG feedback
Note :
1.
P
: Isolated twisted cable wire.
2.
Notation for PG terminals
Terminal
Function
A(+)
A(-)
PG signal input terminal.
The voltage level is (H: 4~12V, L:
≤
1V).
Its Max. frequency is < 32767 Hz
IP12
IG12
Terminals feed in the (+12)VDC external power
source (+12V
±
10%, the Max. current is 40mA)
+12V
0V
(+12)V DC source (+12V
±
10%, min. 0.5A)
E
Inverter ground.
3.
Please refer to page
3-27
and
3-69
for more details on PG feedback.
4.
The A(+), A(-), IP12, IG12 terminals are integrated as CN2 in compact
version. (see page
1-9~1-10
). The code No. of the wire is 4H339D0250001.
5.
The PG interface only allows the open-collector interface drive or
complementary interface drive.
6.
The short pin of TP1 set to PULL UP position for open-collector interface
(factory setting) and set to OPEN position for complementary interface. The
PG interface only allows the open-collector interface drive or complementary
interface drive.
7.
The shielded twisted-pair cable wire should be used between the inverter and
PG, its length should be less than 150 feet.