1-14
1.7 Wiring main circuit and notice
■
Main circuit wiring
The non-fusible-breaker (NFB) should be installed between the AC source and the
R/L1-S/L2-T/L3 input terminal of MA7200 inverter. The user can make his own decision
of installing electromagnetic contactor block (MCB) or not. To protect against the false
triggering of leakage-current, the user should install a leakage current breaker with
amperage sensitivity
≧
200mA and operation time
≧
0.1 sec.
Table 3
230V and 460V class applicable wire size and connector
MA7200 model
Wire size (mm
2
)
Power
supply
Applicable
Power Rating
(HP)
*1
Rated
KVA
Rated
current
(A)
Main
circuit
*2
Ground
connection
wire E (G)
Control
wire
*3
NFB
*4
MCB
*4
1HP
2
4.8
2
~
5.5
2
~
5.5
0.5
~
2
TO-50EC(15A)
CN-11
2HP
2.7
6.4
2
~
5.5
3.5
~
5.5
0.5
~
2
TO-50EC(20A)
CN-11
230
V
1
Φ
/
3
Φ
3HP
4
9.6
3.5
~
5.5
3.5
~
5.5
0.5
~
2
TO-50EC(20A)
CN-11
5.4HP
7.5
17.5
5.5
5.5
0.5
~
2
TO-50EC(30A)
CN-16
7.5HP
10.1
24
8
5.5
~
8
0.5
~
2
TO-100S(50A)
CN-18
10HP
13.7
32
8
5.5
~
8
0.5
~
2
TO-100S(60A)
CN-25
15HP
20.6
48
14
8
0.5
~
2
TO-100S(100A)
CN-50
20HP
27.4
64
22
8
0.5
~
2
TO-100S(100A)
CN-65
25HP
34
80
22
14
0.5
~
2
TO-225S(150A)
CN-80
30HP
41
96
38
14
0.5
~
2
TO-225S(175A)
CN-100
230
V
3
Φ
40HP
54
130
60
22
0.5
~
2
TO-225S(175A)
CN-125
1HP
2.2
2.6
2
~
5.5
2
~
5.5
0.5
~
2
TO-50EC(15A)
CN-11
2HP
3.4
4
2
~
5.5
3.5
~
5.5
0.5
~
2
TO-50EC(15A)
CN-11
3HP
4.1
4.8
2
~
5.5
3.5
~
5.5
0.5
~
2
TO-50EC(15A)
CN-11
5.4HP
7.5
8.7
2
~
5.5
3.5
~
5.5
0.5
~
2
TO-50EC(15A)
CN-18
7.5HP
10.3
12
3
~
5.5
3.5
~
5.5
0.5
~
2
TO-50EC(20A)
CN-18
10HP
12.3
15
5.5
5.5
0.5
~
2
TO-50EC(30A)
CN-25
15HP
20.6
24
8
8
0.5
~
2
TO-50EC(30A)
CN-25
20HP
27.4
32
8
8
0.5
~
2
TO-100S(50A)
CN-35
25HP
34
40
8
8
0.5
~
2
TO-100S(75A)
CN-50
30HP
41
48
14
8
0.5
~
2
TO-100S(100A)
CN-50
40HP
54
64
22
8
0.5
~
2
TO-100S(100A)
CN-65
50HP
68
80
22
14
0.5
~
2
TO-125S(125A)
CN-80
60HP
82
96
38
14
0.5
~
2
TO-225S(175A)
CN-100
460
V
3
Φ
75HP
110
128
60
22
0.5
~
2
TO-225S(175A)
CN-125
*1 : It is assumed constant torque load.
*2 : The main circuit has terminals of R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, B1/P, B2/R, B2,
Θ
.
*3 : The control wire is the wire led to the pin terminals of control board.
*4 : In Table 3, the specified Part No. of NFB and MC are the item No. of the products of TECO. The
customer can use the same rating of similar products from other sources. To decrease the noise
interference, be sure to add R-C surge suppressor (R: 10
Ω
/5W, C: 0.1
µ
F/1000VDC) at the 2