ASTRA-A RPA 

Signaling line extender 

 

User guide

 

 

 

 

 

This user guide is intended to study the principle of operation, proper use, 
storage and maintenance of the signalling line extender Astra-A RPA.  

Abbreviations:  

SLC 

 

Signaling Line Circuit 

Addressable  devices

 

–  Astra-42A  smoke  fire  detectors,  Astra-43A 

heat  fire  detectors,  Astra-45A  fire  manual  call  point,  Astra-BRA  relay 
unit, Astra-MA addressable marks, Astra-BPA 

–  

addressable signal relay unit; 

ILS

 

– short circuit isolator Astra-A ILS;  

Tutorial 

–  tutorial  built  into  the  Astra  Pro  PKM 

Setup  Module,  or  Astra-812  Pro  Setup  Instruc-
tions; 

Control  Panel 

 

control  panel  and  fire  control 

device  Astra-812  Pro  or  Astra-8945  Pro    with 
firmware version v5_6 and higher;  

PKM  Astra Pro 

– 

configuration and monitoring 

software 

(available 

on 

the 

website 

www.teko.biz); 

PC

 

– personal computer ; 

Software

 

 

Configuration and monitoring Soft-

ware; 

RPA

 

– signaling line extender. 

 

1    Function  

 

1.1 

 The RPA is designed to collect information from two SLC lines by 

polling  all  registered  addressable  devices  one  by  one  for  changes  in 
the  state  and  transmitting  this  information  via the  RS-485  interface  to 
the control panel.  

1.2 

 The  number  of  RPA  connected  to  one  control  panel  -  up  to 

16* 

pcs

. (If the built-in radio module of the Control Panel is disabled). 

1.3 

RPA consists of: 

- two RS-485 communication interfaces with built-in isolators for connect-
ing to the control panel* and organizing a ring interface, 
-  two  independent  SLC  interfaces  with  built-in  short  circuit  isolators: 
SLC1 and SLC2, 
- power supply for addressable devices of two SLC with overload pro-
tection, 
- USB port for firmware update. 

1.4 

 RPA  provides  isolation  of  the  SLC  section,  the  RS-485  interface, 

in which a short circuit has occurred.   

1.5 

 RPA provides a setting of the SLC operation mode: 

“Ring  SLC1-SLC2"  mode  (by  default)  -  connection  of  up  to  250  (no 

more  than  96  "Astra-BRA"  and  no  more  than  96  "Astra-BPA"  for  one 
RPA and Control Panel) addressable devices in the "ring" topology, the 
length of the SLC ring is up to 1000 m; 
-

 

"Individually SLC1 and SLC2" - connection of up to 250 addressable 

devices in each SLC (but not more than 250 in total), with the length of 
each SLC up to 1000 m. 

1.6 

RPA  supports  up  to  32*  isolators  to  one  SLC.  In  each  formed  SLC 

segment  (between  adjacent  isolators  or  between  an  isolator  and  RPA) 
there should be no more than 32 addressable devices. The cable length 
in a segment should not exceed 200 m. 

1.7 

Recommended wires for SLC: cable with two pairs of twisted cores 

(pairs arranged in parallel), core cross-section from 0.35 to 2.5 sq. mm. 

For  security  systems,  it  is  permissible  to  use  a  UTP  4×2×0.5  cables. 
Recommended wire type to ensure maximum range for SLC in fire sys-

tems is FRLS (FRHF, FRLSLtx), 2×2×0.5 

1.8 

RPA has two independent power  inputs (main and backup) and 

automatically  switches  from  the  main  input  to  the  backup  and  back 
when the voltage drops.  
RPA  is  powered  from  external  redundant  power  sources  with  a  rated 
voltage of 12 V or 24 V. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
__________________________________ 

*  Provided  in the  Control  Panel  and  RPA  versions  5_6  and  higher,  in 
the settings of the Control Panel, you must set the bitrate to 38400 bps 

2  Specification 

 

Power supply voltage, V

……………………………from 11 to 27  

Consumption, mA, without connecting addressable devices to SLC, 
not more ........................................................................................ 100 
Average  current  consumption  of RPA  when  connected  on  SLC  of ad-
dressable  devices  in  the  amount  of  N  pieces  calculated  according  to 
the formula and is, mA, not more: 
-  when powered by 12 V ..................................................... 200+0.8*N 
-  when powered by 24 V ..................................................... 100+0.4*N 
Peak turn-on current RPA, mA, not more: 
-  when powered by 12 V ............................................................... 850 
-  when powered by 24 V ............................................................... 450 
Output voltage, V ................................................................................. 27

±0.5  

Threshold for the start of indication of a power failure, V ...................... 10 
Boot time, sec., not more................................................................. 10 
Maximum  cable  cross  section  for  connection  to  terminal  blocks,  sq.  mm, 
not more ..................................................................................................... 2.5 
Overall dimensions, mm, not more ................................. 

136 × 85 × 38   

Weight, kg, not more .....................................................................0.14 

 

Operating conditions 

Temperature range, °С ................................................ from -30 to +55 
Relative humidity, % ................................................ up to 93 at +40 

°

С  

                                                              

without moisture condensation

 

3  Delivery set 

 

Astra-A RPA ................................................................................. 1 pc. 
Resistor C1-4-0.5 W-

100 Ohm±5% .............................................. 2 pc. 

Screw ........................................................................................... 4 pc. 
Dowels ......................................................................................... 4 pc. 

 

4  Design 

 

4.1 

RPA  is  designed  in  a  form  of  a  block  consisting  of  a  base  and  a 

removable  cover.  A  PCB  with  radio  elements  is  mounted  inside  the 
block (Pic 2).  

 

Pic. 2 

 

4.2 

Installed on the PCB: 

a)

 LED indicators: 

POWER - 

to control the power state of the RPA; 

FAILURE - 

to control the state of the RPA 

INTERFACE  - 

to  control  the  state  of  the  RS-485  interface  line

 

and  the 

presence of its own registration in the Control Panel; 

SLC

 - to control the status of SLC1 and SLC2, the presence of registered 

devices; 

b)

 tamper switch that generates a "Tampering" notification in case of un-

authorized opening of the case; 

c)

 plugs F1, F2, pad DEL

:

 

- plug F1 - to update firmware,   
- plug F2 - to set the operating mode (service or standby),  
- contact area DEL - to restore factory settings; 

d)

 USB connector (to change firmware) 

e)

 terminal blocks for connecting power supply, Control Panel and two 

signalling lines. 

 

 

 

 

Summary of Contents for ASTRA-A RPA

Page 1: ... cable length in a segment should not exceed 200 m 1 7 Recommended wires for SLC cable with two pairs of twisted cores pairs arranged in parallel core cross section from 0 35 to 2 5 sq mm For security systems it is permissible to use a UTP 4 2 0 5 cables Recommended wire type to ensure maximum range for SLC in fire sys tems is FRLS FRHF FRLSLtx 2 2 0 5 1 8 RPA has two independent power inputs main...

Page 2: ...D2 x2 yellow flashes every 3 sec Connection with Control Panel is normal Activity with Control Panel via D1 and D2 Solid green Status Interface LED Control Panel No connection with Control Panel No activity with Con trol Panel via D1 and D2 Solid yellow No connection with Control Panel No activity with Con trol Panel via D1 x1 yellow flash every 1 sec No connection with Control Panel No activity w...

Page 3: ...a the Astra Pro PKM or the Astra 812 Pro menu 6 2 Removing RPA а If the RPA is connected to the Control Panel then the removal of the RPA from the memory of the Control Panel is done through the Configuration Module of the PKM Astra Pro software or from the menu of the Control Panel Astra 812 Pro b If the RPA is not connected to the Control Panel remove the RPA from the memory of the Control Panel...

Page 4: ...a Pro or on the screen Astra 812 Pro the status of the RPA the sta tus Normal should be displayed 2 Run test mode according to User guide Control the issuance of notifications on the Control Panel 9 4 If the length of the radial topology SLC is more than 800 m it is recommended to install a 100 Ohm terminating resistor from the de livery set at the SLC point farthest from the RPA to match the Data...