3                                                               

rev. RPA-v2_0_en 

Status 

SLC LED 

Control 

Panel  

Data SLC1 failure 

x2 green 

flashes

 every 3 

sec.

  

SLC1 General failure * 

x3 green 

flashes

 every 3 

sec.

  

SLC2 Failure 

x1 yellow 

flash

 every 3 sec. 

Data SLC2 failure 

x2 yellow 

flashes

 every 3 

sec. 

General failure SLC2*  

x3 yellow 

flashes

 every 3 

sec.

 

SLC1 and SLC2 failure 

1/2/3 times green/yellow

 

flashes

 alternation with a pe-

riod of 

3 sec.

 

Software change 

Not on 

«+» - the notification is sent to the Control Panel 

«-» - the notification is not sent to the Control Panel 
______________________________________________________
______________ 
*  notification  is  issued  when  there  is  a  simultaneous  presence  of 
power supply and data line failures.

 

 

6  Prepare for operation  

 

Before starting registration, you should update the version of the 
RPA firmware according to the method of clause 8. 

 

6.1   Adding to the system 

 

 

1) 

Check the position of the jumper on the plug F1, must be removed. 

2) 

Connect RPA to Control Panel via RS-485 interface.  

3) 

Turn on the power supply of  the RPA and Control Panel (if it was 

turned off). 

4) 

Run the Configuration Module utility from the Astra Pro PKM kit on 

the PC. 

5) 

In  the  menu  of  the  Configuration  Module,  select  the  item  "Hard-

wired devices" / "List of hardwired devices". 

6) 

 Place the cursor on the selected free cell of the address from the 

list of devices, right-click to open the menu and select the item "Regis-
ter device". 

7) 

Check in PKM Astra Pro how the registration passed: 

in  case  of  successful  registration  on  the  PC  in  the  program  window, 

the entry “RPA” will appear in the selected line of the list of registered 
devices;in case of unsuccessful registration, it is necessary to repeat 
the registration procedure (steps 6, 7). 

The 

procedure is accompanied by messages: “In progress”, “Complet-

ed” or “Not completed”.

  

Note! 

RPA  is  ready  for  registration  of  detectors  in  it  60  sec  after  the 

power is turned on. 

Attention!

 

Do not turn off the power until the end of registration and config-
uration  of  all  devices  in  the system! 

In  case  of  unsuccessful  regis-

tration, it is necessary to perform the procedure for restoring the RPA 
factory  settings  according  to  the  method  of  clause  7  and  repeat  the 
registration.  

At the end of the registration, if it is necessary to store the RPA for a 
long time before using it at the facility, it is allowed to turn off its power. 
When the power is turned on, re-registration in the same control panel 
is  not  required  if  the  RPA  was  not  forcibly  removed  from  the  control 
panel via the Astra Pro PKM or the Astra-812 Pro menu.  

 

6.2 Removing RPA 

 

а)

  If  the  RPA  is  connected  to  the  Control  Panel,  then  the  removal  of 

the  RPA  from  the  memory  of  the  Control  Panel  is  done  through  the 
Configuration  Module  of  the 

PKM  Astra  Pro

  software  or  from  the 

menu of the Control Panel Astra-812 Pro.   

b)

 If the RPA is not connected to the Control Panel: 

 

remove  the  RPA  from  the  memory  of  the  Control  Panel  via  PKM 

Astra Pro or from the menu of the Control Panel Astra-812 Pro;  

 

reset factory settings of the RPA according to clause 7. 

 

 
 
 

7  Restoring factory settings 

 

1) 

turn on RPA power; 

2) 

remove the RPA cover; 

3) 

close  the  DEL  contact  pad  for  5  sec,  the  INTERFACE  indicator 

should  flash  alternately  yellow  /  green  x1  every  sec,  open  the  DEL 
contact pad when the indication starts ;  

4) 

within 

5 sec

 (while the indication is running), press and release the 

tamper  switch  for 

1  sec

.  On  the 

FAILURE

  indicator,  the 

yellow

 color 

indication will turn on for 

up to 15 seconds

, then 

the “Power-on test” 

indication  will  turn  on.  After  turning  off  the  indication,  the  factory  set-
tings are restored and the RPA is ready for registration.

 

 

8  Firmware update 

Attention!

  

It  is  not  recommended  to  update  the  software  of  a  working  RPA 
with  registered  detectors  without  special  instructions  from  tech-
nical support specialists.

 

Actions needed: 

1) 

install  on  the  PKM  Astra  Pro  computer  according  to  the  method  of 

the  Astra  Pro  software  package  (PKM)  (located  on  the  website 
www.teko.biz). 

2) 

Turn off the RPA power; 

3) 

remove the RPA cover; 

4) 

install a jumper on the F1 plug

;

 

5) 

turn on RPA power; 

6) 

connect RPA to PC USB; 

7) 

run the Firmware update module of the Astra Pro PKM; 

8) 

select the firmware file with the required version and start the firm-

ware update procedure; 

9) 

after  completing  the  firmware  update  procedure,  turn  off  the  RPA 

power, close the Firmware update module; 

10) 

 disconnect RPA from PC USB; 

11) 

 remove the jumper from the plug F1; 

12) 

 turn on the power (if necessary). 

 

9  Installation 

 

9.1 

The wires of the power supply circuits and the RS-485 RPA inter-

face should be located away from powerful power and high-frequency 
cables. 

9.2 

When  installing,  it  is  allowed  to  use  mounting  devices  (cabinets, 

boxes, etc.) 

9.3  Installation procedure 

 

1  

 

Push  the  base  latch  out  of  the  slot 
in the cover. Remove the cover

 

 

Remove  the  PCB  by  unscrewing  the 
screw securing the PCB to the base

 

3

 

 

Make  markings  at  the  attachment  point, 
using  the  RPA  base  as  a  stencil.  Pass 
the wires for power supply, interface and 
data  communication  lines  through  the 
wire entry holes in the base of the RPA. 
Fix the base in the place chosen for this.

 

 

4

  Install  the  PCB  in  place;  tighten  the  screw  that  secures  it  to  the 

base. 

Summary of Contents for ASTRA-A RPA

Page 1: ... cable length in a segment should not exceed 200 m 1 7 Recommended wires for SLC cable with two pairs of twisted cores pairs arranged in parallel core cross section from 0 35 to 2 5 sq mm For security systems it is permissible to use a UTP 4 2 0 5 cables Recommended wire type to ensure maximum range for SLC in fire sys tems is FRLS FRHF FRLSLtx 2 2 0 5 1 8 RPA has two independent power inputs main...

Page 2: ...D2 x2 yellow flashes every 3 sec Connection with Control Panel is normal Activity with Control Panel via D1 and D2 Solid green Status Interface LED Control Panel No connection with Control Panel No activity with Con trol Panel via D1 and D2 Solid yellow No connection with Control Panel No activity with Con trol Panel via D1 x1 yellow flash every 1 sec No connection with Control Panel No activity w...

Page 3: ...a the Astra Pro PKM or the Astra 812 Pro menu 6 2 Removing RPA а If the RPA is connected to the Control Panel then the removal of the RPA from the memory of the Control Panel is done through the Configuration Module of the PKM Astra Pro software or from the menu of the Control Panel Astra 812 Pro b If the RPA is not connected to the Control Panel remove the RPA from the memory of the Control Panel...

Page 4: ...a Pro or on the screen Astra 812 Pro the status of the RPA the sta tus Normal should be displayed 2 Run test mode according to User guide Control the issuance of notifications on the Control Panel 9 4 If the length of the radial topology SLC is more than 800 m it is recommended to install a 100 Ohm terminating resistor from the de livery set at the SLC point farthest from the RPA to match the Data...

Reviews: