3
rev. RPA-v2_0_en
Status
SLC LED
Control
Panel
Data SLC1 failure
x2 green
flashes
every 3
sec.
+
SLC1 General failure *
x3 green
flashes
every 3
sec.
+
SLC2 Failure
x1 yellow
flash
every 3 sec.
+
Data SLC2 failure
x2 yellow
flashes
every 3
sec.
+
General failure SLC2*
x3 yellow
flashes
every 3
sec.
+
SLC1 and SLC2 failure
1/2/3 times green/yellow
flashes
alternation with a pe-
riod of
3 sec.
+
Software change
Not on
-
«+» - the notification is sent to the Control Panel
«-» - the notification is not sent to the Control Panel
______________________________________________________
______________
* notification is issued when there is a simultaneous presence of
power supply and data line failures.
6 Prepare for operation
Before starting registration, you should update the version of the
RPA firmware according to the method of clause 8.
6.1 Adding to the system
1)
Check the position of the jumper on the plug F1, must be removed.
2)
Connect RPA to Control Panel via RS-485 interface.
3)
Turn on the power supply of the RPA and Control Panel (if it was
turned off).
4)
Run the Configuration Module utility from the Astra Pro PKM kit on
the PC.
5)
In the menu of the Configuration Module, select the item "Hard-
wired devices" / "List of hardwired devices".
6)
Place the cursor on the selected free cell of the address from the
list of devices, right-click to open the menu and select the item "Regis-
ter device".
7)
Check in PKM Astra Pro how the registration passed:
in case of successful registration on the PC in the program window,
the entry “RPA” will appear in the selected line of the list of registered
devices;in case of unsuccessful registration, it is necessary to repeat
the registration procedure (steps 6, 7).
The
procedure is accompanied by messages: “In progress”, “Complet-
ed” or “Not completed”.
Note!
RPA is ready for registration of detectors in it 60 sec after the
power is turned on.
Attention!
Do not turn off the power until the end of registration and config-
uration of all devices in the system!
In case of unsuccessful regis-
tration, it is necessary to perform the procedure for restoring the RPA
factory settings according to the method of clause 7 and repeat the
registration.
At the end of the registration, if it is necessary to store the RPA for a
long time before using it at the facility, it is allowed to turn off its power.
When the power is turned on, re-registration in the same control panel
is not required if the RPA was not forcibly removed from the control
panel via the Astra Pro PKM or the Astra-812 Pro menu.
6.2 Removing RPA
а)
If the RPA is connected to the Control Panel, then the removal of
the RPA from the memory of the Control Panel is done through the
Configuration Module of the
PKM Astra Pro
software or from the
menu of the Control Panel Astra-812 Pro.
b)
If the RPA is not connected to the Control Panel:
remove the RPA from the memory of the Control Panel via PKM
Astra Pro or from the menu of the Control Panel Astra-812 Pro;
reset factory settings of the RPA according to clause 7.
7 Restoring factory settings
1)
turn on RPA power;
2)
remove the RPA cover;
3)
close the DEL contact pad for 5 sec, the INTERFACE indicator
should flash alternately yellow / green x1 every sec, open the DEL
contact pad when the indication starts ;
4)
within
5 sec
(while the indication is running), press and release the
tamper switch for
1 sec
. On the
FAILURE
indicator, the
yellow
color
indication will turn on for
up to 15 seconds
, then
the “Power-on test”
indication will turn on. After turning off the indication, the factory set-
tings are restored and the RPA is ready for registration.
8 Firmware update
Attention!
It is not recommended to update the software of a working RPA
with registered detectors without special instructions from tech-
nical support specialists.
Actions needed:
1)
install on the PKM Astra Pro computer according to the method of
the Astra Pro software package (PKM) (located on the website
www.teko.biz).
2)
Turn off the RPA power;
3)
remove the RPA cover;
4)
install a jumper on the F1 plug
;
5)
turn on RPA power;
6)
connect RPA to PC USB;
7)
run the Firmware update module of the Astra Pro PKM;
8)
select the firmware file with the required version and start the firm-
ware update procedure;
9)
after completing the firmware update procedure, turn off the RPA
power, close the Firmware update module;
10)
disconnect RPA from PC USB;
11)
remove the jumper from the plug F1;
12)
turn on the power (if necessary).
9 Installation
9.1
The wires of the power supply circuits and the RS-485 RPA inter-
face should be located away from powerful power and high-frequency
cables.
9.2
When installing, it is allowed to use mounting devices (cabinets,
boxes, etc.)
9.3 Installation procedure
1
Push the base latch out of the slot
in the cover. Remove the cover
2
Remove the PCB by unscrewing the
screw securing the PCB to the base
3
Make markings at the attachment point,
using the RPA base as a stencil. Pass
the wires for power supply, interface and
data communication lines through the
wire entry holes in the base of the RPA.
Fix the base in the place chosen for this.
4
Install the PCB in place; tighten the screw that secures it to the
base.