4-23
11.
1-00~05=14 Main/sub Frequency Command Selection
When External multifunction input terminals are off, the inverter Frequency Command is operated
by 00-05.
When External multifunction input terminals are on, the inverter Frequency Command is operated
by 00-06.
12.
01-00~05=15(PID Function Disable)
When the PID Function Disable is ON, PID is not controlled by 09-00.
13.
01-00~05=16 (Integration Value Resets to Zero)
When the multifunction terminal 01-00~05 is set at 16 and the input terminal is on , the
Integration Value of PID Resets to Zero .
14. 01-00~05=17(Reset Command)
The Reset command is same as the Reset Key on the panel. When the command is OFF, the
inverter does not respond.
15. 01-00~05=18 (Power Source Detect for KEB)
Please refer to 4-11description.
16. 01-00~05=19(Auto _ Run Mode)
The function of auto-run is like a simple built-in PLC function, when the extermal terminal
function is set to 19, and turns on. Autorun function will be executed according to group
13.( Please refer to group13)
17. 01-00~05=20(Counter Trigger Signal)
when the extermal terminal s6 is set a function of 20,after turning it on then off once the counter
value increase 1.
In vector mode, the extermal terminal S6 function of "counter trigger signal input" is disabled.
18. 01-00~05=21(Counter Reset)
When anyone of the extermal terminals S1~S6 is set a function of 21 and turned on, the counter
value will be cleared, and display "c0000", only after this signal turns off, the inverter can
receive trigger signal and count up.
Digital /Analog input signal scan times
:
01-06: Multifunction terminal S1
~
S6 confirm the scan times (x 4ms),1~200 times
1. TM2 terminal is used for scanning. If there are the same signals continuously input for N times, the
inverter will treat the signal as normal. During the signal evaluation, if the scan times are less than N,
the signal will be treated as noise.
2. Each scan period is 4ms.
3. The user can specify the scan times interval duration according to the noise environment. If the
noise is serious, increase the value of 01-06, however the response will be slower.
Signal output with10-17
counter value is attained.
The trigger timing can't be less than
1.5ms.
Counter trigger signal
Multi-function input termin
1.5ms
c0000 c0001 c0002 c0003 c0004 c0005 c0001 c0002
Indication value
10-17=5
11-07=1