4-34
Group 08 Protection Parameters
Code
Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
SLV
PM
SLV
08-48 Selection of Fire Mode
0:Disable
1:Enable
0
O
O
O
08-49
Multi-Function Input
Terminal Status of Fire
Mode
0:Reset after Power Off
1:Reset after Terminal Removed
0
O
O
O
08-50
Multi-Function Terminal
Status of Fire Mode
xxx0b:S6 A Contact
xxx1b:S6 B Contact
0000b
-
O
O
O
08-51
Motor Speed Setting
Source of Fire Mode
0:Fire Mode Speed(08-52)
1:PID Control
2:AI2
0
-
O
O
O
08-52
Motor Speed of Fire
Mode
0.00~100.00
100.00 %
O
O
O
08-53
PID Detection Level of
Fire Mode
0~100
0
%
O
O
O
08-54
Delay Time of Fire
Mode PID Loss
0.0~10.0
0.0
s
O
O
O
08-55
PID Feedback Loss
Detection Selection of
Fire Mode
0:Keep Running
1:Fire Mode Speed(08-52)
2:Max. Output Frequency of Motor 1 (01-02)
0
-
O
O
O
08-56
Detection Level of Fire
Mode AI2 Signal
0~100
0
%
O
O
O
08-57
Delay Time of Fire
Mode AI2 Signal Loss
0.0~10.0
0.0
s
O
O
O
08-58
Selection of Fire Mode
AI2 Signal Loss
0:Keep Running
1:Fire Mode Speed(08-52)
2:Maximun Output Frequency (01-02)
0
-
O
O
O
08-59
Fire Mode Motor
Direction
0:Forward
1:Reverse
0
-
O
O
O
08-60 Fire Mode Password
00000~65534
0
-
O
O
O
***STO function only be designed in EMC filter built-in models.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......