4-60
Enhance the Riding Confort of Elevator
If there is any uncomfortable feeling during acceleration and deceleration period when you take the elevator.
Please try to adjust the parameters as follows.
11-04
11-05
11-06
11-07
Output
Frequency
DC injection braking at stop
(When you use PG vector control,
it will be zero control)
00-14
Acceleration1
00-15
Deceleration1
Notes:
During the deceleration of S curve, if the output frequency is lower than 01-08, the function of S curve will be
stopped and then transfer to DC injection braking (Zero Speed Control).
Function of DC Injection Braking and Zero Speed Control.
ON
Output
Frequency
OFF
OFF
ON
Frequency
Output
DC Brake
07-08(DC Injection Braking Time at Stop)
(Zero Speed Braking Time at Stop)
0.3 ~0.5 s
Note 1:
According to the standards of European market, when the elevator is stop, the inverter and the motor has to be
separated by contactor. For emergency situation, the inverter and the motor just can be separated by DC injection
braking disabled and base block enabled (base block signal is ON)
Note 2:
When inverter control is separated from motor control or DC injection braking control (Zero speed control).
Sometimes, inverter will occur fault by pulse voltage.
Besides, when the contactor is installed between inverter and motor, please et 08-10=1 (Selection of output phase
loss protection).
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......