Alternative RUN Command Selection
Range
【0】:Forward/Stop-Reverse/Stop
【1】:Run/Stop- Reverse/ Forward
【2】:3 Wire Control Mode - Run/Stop
00-04 is valid when run command is set to external mode by 00- 02/00- 03 =1.
Set 00-04=【0/1】first, before setting (03- 00~03- 05) to【0】or【1】.
00- 04=【0】, Set external terminals (03-00 to 03-05) function to 0 for FWD/Stop or Set to 1 for
REV/Stop.
00- 04=【1】, Set external terminals (03-00 to 03-05) function to 0 for Run/Stop or Set to 1 for
FWD/REV
00-04 =【2】Terminals S1, S2, S3 are used in a combination to enable 3 wire run/stop mode.
Settings for 03-00, 03-01, 03–02 will not be effective. Please refer Fig.4.3.1 for 2 wire operation
mode.
2-wire operation
For 2-wire operation set 03-00 (S1 terminal selection) to 0 and 03-01 (S2 terminal
selection) to 1.
Figure 4.3.1 wiring example of 2-wire
3-wire operation
Figure 4.3.2 3 wiring example of 3-wire