4-65
Figure 4.3.4 Analog input as main frequency reference command
Note:
1.
When analog current input signal connectes to AI2, please set JP3 to I (default setting) and set
04-00=0~3 (AI2=0~20mA / 4~20mA)。
2.
When analog voltage input sognal connectes to AI2, please set JP3 to V (default setting) and
set 04-00=0~3 (AI2=0~10V / 2~10V)。
3.
Please set parameter 04-00 correctly according to your AI1/AI2 signal.
(4)
00-05/00-06=4
The inverter accelerates with the UP command closed and decelerates with the DOWN
command closed. Please refer to parameter 03-00~03-05 for additional information.
(5)
00-05/00-06=5
Please use MODICON series PLC or othe devices which uses MODBUS protocol to
communicate, please set thecorrect baud-rate for communication according to the details in
chapter 09.
(6)
00-05/00-06=7
To use this function a pulse train input is required to be connected to the PI input and
GND, please refer the photo as Fig.4.3.5. PI input terminal, built-in resistance, is not required to
connect the resistance if open collector input mode is used
Figure 4.3.5 Frequency reference from pulse input
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......