4-113
During run:
When an external base block command is activated, the keypad displays "BBn BaseBlock (Sn)",
indicating the inverter output is turned off (n indicates the digital input number 1 – 8). Upon
removing the base block signal, the motor will run at the frequency reference. If speed search from
frequency reference is active the inverter output frequency starts from the frequency reference and
searches for the coasting motor speed and continue to operate. If speed search is not active the
output frequency starts at 0Hz.
During deceleration:
When an external base block command is activated, the keypad displays "BBn BaseBlock (Sn)",
indicating the inverter output is turned off (n indicates the digital input number 1 – 8). Upon
removing the base block signal, the motor is stopped or will coast to a stop and the inverter will
remains in the stop condition.
During acceleration:
When an external base block command is activated, the keypad displays "BBn
BaseBlock (Sn)", indicating the inverter output is turned off (n indicates the digital input number 1 –
8). Upon removing the base block signal, the motor will run at the frequency reference. If speed
search from frequency reference is active the inverter output frequency starts from the frequency
reference and searches for the coasting motor speed and continue to operate. If speed search is not
active the output frequency starts at 0Hz.
Please refer figure 4.322 for external base block operation。
Figur 4.3.22 External base block operation
(18)
PID control disabled (03-0X =16)
(19)
Fault reset (03-0X =17)
The output becomes active when the inverter trips on a fault. Upon an inverter fault the inverter
output will turn off (base block) and the keypad displays the dedicated fault message. When
fault occurs, the following actions can be used to reset the fault:
(a)
One of the multi-function digital inputs (03-00 to 03-05) to 17 (reset fault) and active input.
(b)
Press the reset key of the digital operator (RESET).
*
(c)
Recycle power to the inverter.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......