4-115
(29)
Local/Romote selection (03-0X=27)
Switch the inverter frequency reference source between Local (keypad) or Remote (control
circuit terminals or RS485). Use parameter 00-05 (Main frequency command source selection)
and 00-02 (Run command selection) to select the remote source.
Local/Remote function can be set by one of digital inputs (S3~S6), and be switched by
03-03~03-05 which the parameter setting is to
“
27
”
.In 3 wire operation control, S1/S2/S3 are
reserved for run/stop/forward-reverse operation, please refer the table below.
Note:Local and remote mode only can be switched when inverter stop running.
Input
Mode
Frequency Reference & Run/Stop Command Source
ON
Local
mode
Frequency eference and Run-Stop from keypad.
LEDs SEQ and REF are off.
OFF
Remote
mode
Frequency reference source selected by parameter 00-05
and Run/Stop source selected by parameter 00-02
LEDs SEQ and REF are on.
(30)
Local/Romote selection (03-0X=28)
In Remote mode, indicators of SEQ and REF are on; you can use terminals AI1 and AI2 to
control the frequency command, and use terminals S1, S2 or communication terminal RS-485
to control the operation command.
When one of 03-02~03-05=28 (Remote mode selection),inverter can switch between external
terminal source (S1~S6) or communication (RS-485) source. Please refer the figure 4.3.23。
Figure 4.3.23 Remote mode operation selection
(31)
Jog Frequency Selection (03-0X=29)
When jog frequency selection is on, the inverter will depend on the parameter 00-18 (jog
frequency) as the command.
(32)
DC Braking (03-0X=33)
When DC-Injection braking is enabled during start and stop of the inverter.
DC injection braking is disabled when a run or jog command is active.
Refer to the DC braking time diagram in Figure 4.3.24.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......