PID Control Disable 2 (03-0X=66)
(41)
External Fault (03-0X=68)
When this function is enabled, inverter will stop running and motor will coast to stop.
When digital input (S3) set to external fault, keypad will display
“
EF3 Ext. Fault (S3)
”.
All digital input terminals can be set to external fault.
(42)
Externl Overload (03-0X=69)
When this function is enabled, inverter will stop running and motor will coast to stop.
When digital input (S5) set to external fault, keypad will display
“
TOL Ext. OverLoad
”
Fire mode needs to be enabled first (08-48=1) when external overload function needs to be
used. Only S5 terminal can be set to external overload input.
External overload function will be set to normal close contact. Pleae do not set run command
from external source.
03- 06
UP/DOWN Frequency Step
Range
【0.00~5.00】
Hz
When 03-06=0Hz, UP/DOWN function will be kept.
When 03-06≠0Hz, frequency command becomes operation frequency plus 03-06 value.
Example:
03- 00=8 (S1 terminal is increasing frequency command)
03- 01=9 (S2 terminal is decreasing frequency command)
03- 06=
△
Hz
Mode 1:
When 03-06=0, UP/DOWN function will be kept.
Mode 2:
When 03-06
≠
0 and the turned on period is less than 2 secs, for every ON operation frequency
changes by
△
Hz.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......