4-119
03- 07
UP/DOWN Keep Frequency Status after Stop Command
Range
【0】
:When UP/DOWN is used, the preset frequency is held as the inverterstops,
and the UP/DOWN function is disable.
【1】
:When UP/DOWN is used, the preset frequency is reset to 0 Hz as the
inverter stops.
【2】
:When UP/DOWN is used, the preset frequency is held as the inverter
stops, and the UP/DOWN is available.
【3】
:When acceleration is used, the output frequency will be updated.
03-07=0, When run signal is removed (Stop Command), the output frequency is stored in
parameter 05-01( Key pad Frequency).
03-07=1, when run command is removed, the output frequency of deceleration will be clear.
03-07=2, when run command is not available, the UP/DOWN command will be written into
frequency command.
03-07=3, when frequency command is used, then resend the run command, the frequency
command will be updated by operation frequency when you press UP/DOWN key.
03- 08
S1~S6 scan time confirmation
Range
1~200ms
Multifunction input terminal On/Off periods will be scanned for the number of cycles according to
the set value in parameter 03-08. If the signal status for ON or OFF period is less than the set
period it will be treated as noise.
Use this parameter if unstable input signal is expected, however setting long scan time periods
results in slower response times.
03- 09
S1~S4 switch type select
Range
【
xxx0b
】:
S1 A Contact 【xxx1b
】:
S1 B Contact
【
xx0xb
】:
S2 A Contact
【xx1xb
】:
S2 B Contact
【
x0xxb
】:
S3 A Contact
【
x1xxb
】:
S3 B Contact
【
0xxxb
】:
S4 A Contact
【1xxxb
】:
S4 B Contact
03- 10
S5~S6 switch type select
Range
【
xxx0b
】:
S5 A Contact
【xxx1b
】:
S5 B Contact
【
xx0xb
】:
S6 A Contact
【xx1xb
】:
S6 B Contact
Parameter 03-09 and 03-10 selects the digital input type between a normally open and a normally
closed switch/contact.
Each bit of 03-09/03-10 presents an input:
03-09=
0
0
0
0
0 :normally open switch
s4
s3
s2
s1
1 :normally close switch
03-10=
0
0
0
0
0 :normally open switch
s6
s5
1 :normally close switch
Example:
S1 and S2 wired to a normally closed contact/switch set 03- 09=0011
。
Note:
Do not set the operation command parameter 00-02 to terminal control before setting the digital
input type. Failure to comply may cause death or serious injury.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......