4-121
Table 4.3.29 Function table of multi-function digital output
Value
Function
Contents
Control mode
Name
LCD display
V/F SLV
PM
SLV
0
During Running
Running
ON:Dring running (Run command is ON)
O
O
O
1
Fault Contact Output Fault
ON:Fault contact output (except CF00 and
CF01)
O
O
O
2
Frequency Agree
Freq. Agree
ON:Frequency agree (frequency agree width
detection is set by 03-14 )
O
O
O
3
Setting Frequency
Agree (03-13 ±
03-14)
Setting Freq Agree
ON:Output frequency = allowed frequency
detection level (03-13) ± frequency
bandwidth (03-14)
O
O
O
4
Frequency Detection
1 (≧ 03-13, hysteresis
range is the setting
value of 03-14)
Freq. Detect 1
ON:Output frequency > 03-13, Hysteresis
range is 03-14
O
O
O
5
Frequency Detection
2 (≦03-13, hysteresis
range is the setting
value of 03-14)
Freq. Detect 2
OFF:Output frequency > 03-13, Hysteresis
range is 03-14
O
O
O
6
Automatic Restart
Auto Restart
ON:the period of automatic restart
O
O
O
7
Momentary AC
Power Loss
Invalid Do Func.
Reserved
O
O
O
8
Rapid Stop
Invalid Do Func.
Reserved
O
O
O
9
Base Block
Baseblock
ON:During Baseblock
O
O
O
10
Motor Overload
Protection (OL1)
Invalid Do Func.
Reserved
O
O
O
11
Drive Overload
Protection (OL2)
Invalid Do Func.
Reserved
O
O
O
12
Over Torque
Threshold Level (OL3)
Over Torque
ON:Over torque detection is ON
O
O
O
13
Preset Output
Current Reached
Currebt Agree
ON:When output current > 03-15 is ON
O
O
O
14 Brake Control
Invalid Do Func.
ON:Mechanical braking release frequency
OFF:Mechanical braking run frequency
O
O
O
15
PID Feedback Signal
Loss
Invalid Do Func.
Reserved
O
O
O
16
Single Pre-set Count
(03-22~03-23)
Invalid Do Func.
Reserved
O
O
O
17
Dual Pre-set Count
(03-22~03-23)
Invalid Do Func.
Reserved
O
O
O
18
PLC Status Indicator
(00-02)
PLC statement
ON:When 00-02 is set to 3
(PLC operation command source)
O
O
O
19 PLC Control
Control From PLC ON:Control from PLC
O
O
O
20 Zero Speed
Zero Speed
ON:Output frequency < Minimum output
frequency (Fmin)
O
O
O
21 Reserved
Reserved
Reserved
-
-
-
22 Reserved
Reserved
Reserved
-
-
-
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......