4-123
Output is active when the output frequency falls within the frequency detection width
(03-14) of the set frequency detection level (o3-13)
(4)
Setting Frequency Agree (03-13 ± 03-14) (03-1X=3)
Output is active when the output frequency falls within the frequency detection width
(03-14) of the set frequency detection level (o3-13).
(5)
Frequency Detection 1 (≧ 03-13, hysteresis range is the value of 03-14) (03-1X=4)
Output is active when the output frequency rises above the frequency detection level (03-13) +
frequency detection width (o3-14) and deactivates when the output frequency falls below
frequency detection level (o3-13).
(6)
Frequency Detection 2 (≦ 03-13, hysteresis range is the value of 03-14) (03-1X=5)
Output is active when the output frequency is below the frequency detection level
(03-13) + frequency detection width (03-14) and turns off when the output frequency
falls below frequency detection level.
(7)
Automatic restart (03-1X=6)
Output is active during an auto-restart operation.
(8)
Momentary AC Power Loss (03-1X=7)
Output is active during momentary AC power loss.
(9)
Rapid Stop (03-1X=8)
Output is active during a rapid stop.
(10)
Base Block (03-1X=9)
Output is active when the inverter output is turned off during a Baseblock command.
(11)
Motor Overload Protection (OL1) (03-1X=10)
Output is active during an overload detection of motor.
(12)
Drive Overload Protection (OL2) (03-1X=11)
Output is active during an overload detection of inverter.
(13)
Over Torque Threshold Level (OL3) (03-1X=12)
Output is active during an over torque detection of inverter.
(14)
Preset Output Current Reached (03-1X=13)
When output current > 03-15 and output current > 03-15 duration > 03-16, it is ON.
(15)
Brake Control (03-1X=14)
Output is active when the brake control is active.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......