4-124
(16)
PID Feedback Signal Loss (03-1X=15)
Output is active when PID feedback signal loss.
(17)
PLC Status Indicator (03-1X=18)
Output is active when operation command parameter 00-02 is set to PLC control.
(18)
PLC Control (03-1X=19)
Output is controlled by the PLC logic.
(19)
Zero Speed (03-1X=20)
When zero speed is active, output frequency < minimum output frequency (01-08).
When zero speed is off, output frequency ≧ minimum output frequency.
ON
OFF
01-08 (Fmin)
Output
Frequency
Zero Speed
t
t
Figure 4.3.26 Zero speed operation
(20)
Motor 2 Selection (03-1X=30)
Output is active when motor 2 is selected.
(21)
Detection Output of PID Feedback Loss (03-1X=37)
Output is active when PID feedback loss.
(22)
Turn On Short Circuit Braking (03-1X=54)
Output is active when truning on short circuit braking.
(23)
Low Current Detection (03-1X=55)
Output is active when low current detection function is active.
(24)
OH Detection (03-1X=59)
Output is active when temperature setting is agreed.
03-13
Frequency detection Level
Range
【0.0~599.0】 Hz
03-14
Frequency detection width
Range
【0.1~25.5】 Hz
Frequency detection level:the multi-function output terminals R1A-R1C, R2A-R2C or PH1
(03-11, 03-12) to the desired detection level and bandwidth for use with multi-function output
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......