4-126
Function
Detection operation of frequency
confirmation
Description
03-15
Current Agree Level
Range
【0.1~999.9】A
03-16
Delay Time of Current Agree Detection
Range
【0.1~10.0】 Sec
When 03-11=13 and then when the output current > 03-15, output relay will active.
03-15:The suggest setting value is 0.1 to motor rated current.
03-16:The delay time performs depending one the setting value.
When output current lower than 03-53
, delay time from ON to OFF in the signal of relay is
100ms (constant).
Time diagram:
03-17
Machanical Braking Release Level
Range
【0.00~20.00】 Hz
03-18
Machanical Braking Level Set
Range
【0.00~20.00】 Hz
When 03-11=14,
In acceleration mode, output relay will be ON as soon as the actual output frequency
reaches the external brake release set in parameter 03-17.
In deceleration mode, output relay will be OFF as soon as the actual output frequency
reachesthe external brake engage level set in parameter 03-18.
Timing diagram for 03-17
≤
03-18 is shown below.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......