4-128
Example:
S2、S4、S6 terminal decided to internal multi-function terminal (decided by 03-21)
S1、S3、S5 terminal decided to external multi-function terminal (remote control)
Please set 03-20=101010, summarized the total value of 03-20 is 42 (32+8+2=42).
03- 21
Action to Set The Internal Multi-Function Input Terminals
Range
【
0~63
】
Each bit of 03- 21 means:
03- 21=
0
0
0
0
0
0
S6
S5
S4
S3
S2
S1
0:Internal Multi-function terminal opened
1:Internal Multi-function terminal closed
Example:
If we need to set S2, S4 closed and S1, S3, S5, S6 opened, please set 03- 21=001010.
summarized the total value of 03-21 is 10 (8+2=10).
03- 22
Setting Counter Agree
Range
【0~9999】
03- 23
Specify Setting Counter Agree
Range
【0~9999】
03-22 is used to set the counter value for internal counter, the counter can be enabled by one
of multi-digital inputs (03-00~03-05 set to 22), when counter value equal to the value of 03-22,
connter value will be reset.
If the counter needs to re-count when 03-22 value not reached setting value, please set one the
multi-digital input to 23 (03-00~03-05=23).
The status of counter can be monitoring by 12-00=0008.
Refer to the photo below, if 03-11=17 (Dual Pre-set Count), 03-22=4 (Pre-Set Count 1),03-23=2
(Pre-Set Count 2). When counter cumulative to 2, RY1 will be active. When counter value
cumulative to 4, the counter value will be reset when trigged signal is removd.
If 03-12=16 and 03-22=4, when counter cumulative to 4, RY2 will be active when trigged signal
is removd.
03-22 value must be higher than 03-23.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......