Auto Run Mode for Single Cycle (06-00=3,6)
The speed of final step will be held to run. (The final step must be put in stage 15)
All other parameters are set same as
“
Example 1
”
shown above.
Freq.
50 Hz
30 Hz
15 Hz
20 Hz
20s
25s
30s
40s
05-01
06-01
06-02
06-15
06-16
06-17
06-18
06-31
Figur 4.3.54 Auto Run Mode for Single Cycle
When 06-00=1~3:After a restart, it continues to run from the unfinished step.
When 06-00=4~6:After a restart, it will begin a new cycle.
06-00
1~3
4~6
Output Frequency
time
Output
Frequency
Run
Command
Continue running from
unfinished step
stop
run
run
time
Output
Frequency
Run
Command
begin a new cycle
stop
run
run
ACC/DEC time in Auto run mode will be according to the setting of 00-14/00-15.
For Auto sequence 0.The run frequency will be according to keypad frequency set by parameter
05-01.Parameters 06-16 and 06-31 are used to set the sequence Run time and Run direction.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......