4
-
150
(1)
07-09=0:Deceleration to stop
When a stop command is issued, the motor will decelerate to the minimum output frequency
(01-08) Fmin and then stop. Deceleration rate depends on the deceleration ime
(factory default is 00-15).
When the output frequency reaches the DC braking stop frequency (07-06) or the minimum
output frequency (01-08), DC injection braking is activated and the motor stops.
S curve setting will add to the overall stop time, refer to figure 4.3.58
Run
Stop
Deceleration ramp to stop
T
Run
Command
Output
Frequency
07-06
Time
Time
T: DC braking time at stop (07-08)
Figure 4.3.58 Deceleration to stop
(2)
07-09=1:Coast to stop
When a stop command is issued, the motor will coast to a stop. Stop time depends on motor
load and friction of the system.
The inverter waits for the time set in the minimum baseblock time (07-18) before accepting the
next run command.
In SLV mode (00-00=2) the speed search function is automatically enabled upon the next run
command.
If the mechanical barking will be used to stop the motor when run command is
removed, please set 07-26=1.
Figure 4.3.59 Coast to Stop
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......