07-09=2:DC braking to stop
When a stop command is issued, the inverter will turn off the output (Baseblock) and after the
minimum Baseblock time (07-18) has expired activate DC braking (07-07).
The DC braking time (t
DCDB
) of Figure 4.4.60 is determined by the value of 07-08 (DC Braking
start time) and the output frequency at the time the stop command was issued.
Increase the minimum Baseblock time (07-18) in case an Overcurrent trip occurs during the DC
braking.
Figure 4.3.60 DC braking to stop
(4)
07-09=3:Coast to stop with timer
When a stop command is issued the motor will coast to a stop after the minimum
Baseblock time (07-18) has expired. The inverter ignores the run command until the
total time of the timer has expired.
The total time of the timer is determined by the deceleration time (00-15, 17,
22 or 24
) and the
output frequency upon stop.
Refer to figure 4.3.61.
Figure 4.3.61 Coast to stop with timer