4
-
165
(5)
The resistor (PTC) conform the British Standards Institution:
When Tr is 150 ℃in Class F and is 180℃ in Class H
Tr-5℃:R
T
≦ 550Ω,put R
T
in formula (1), the V value by calculation is the value of 08-43.
Tr+5℃:R
T
≧1330Ω,put R
T
in formula (1), the V value by calculation is the value of 08-44.
(6)
It gets reference value by using formula (1) even in the different spec of resistor (PTC).
(7)
Please follow the rule of PTC protection function setting, prevent the error occors.
PTC restart level(08-43) > PTC warning level(08-44) > PTCprotection level(08-42)
1330
550
Resistance (O)
Temperature
Class F
150
蚓
Class H
180
蚓
Tr'
Tr - 5
Tr
Tr + 5
Tr: Temperature threshold value
(a) PTC Thermistor Characteristics
(b) PTC Thernistor
connections
Divider Resistor(R)
(1~2K(O)
PTC Thermistor
+ 10V
AI 2
GND
Internal circuit
200KO
Figure 4.3.65 (a) PTC Thermistor Characteristics (b)PTC Thermistor Connections
Notes:
For PTC thermistor connections, JP3 switch needs to set V, 04-00 needs to ser 2 or 4.
08 - 48
Selection of Fire Mode
Range
【0】: Disable
【1】: Enable
When 08-48=0, Fire Mode is disabled.
When 08-48=1, Fire Mode is enabled.
When fire mode is enabled, S6 will be defined to digital input of fire mode (03-0X=47).
When fire mode is enabled, inverter will become to fire mode. No matter inverter is running or
stopping, run and frequency command source will be covered by the setting of fire mode, keypad
display will show
“
FIRE
”
, some of protect functions will be ignored, please refer the table 4.3.35,
inverter will not stop.
When fire mode (03-0X=47) and outour overload (03-0X=68) function is triggered, the other digital
inputs will be ignored, the parameters just can be read by communication or keypad display.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......