4
-
169
Group 09 Communication Parameters
09- 00
INV Communication Station Address
Range
【
1~254
】
09- 01
Communication Mode Selection
Range
【0】:
MODBUS
【1】:
BACNet
09- 02
Baud Rate Setting (bps)
Range
【2】:
4800
【3】:
9600
【4】:
19200
【5】:
38400
09- 03
Stop Bit Selection
Range
【0】:
1 stop bit
【1】:
2 stop bits
09- 04
Parity Selection
Range
【0】:
No Parity
【1】:
Even bit
【2】:
Odd bit
09- 05
Communication Data Bit Selection
Range
【0】:
8 Bit Data
【1】:
7 Bit Data
09- 06
Communication Error Detection Time
Range
【
0.0~25.5
】
Sec
09- 07
Fault Stop Selection
Range
【0】:
Deceleration to stop based on deceleration time 1
【1】:
Coast to stop when communication fault occurs
【2】:
Deceleration to stop based on deceleration time 2
【3】:
Keep operating when communication fault occurs
09- 08
Comm. Fault Tolerance Count
Range
【
1~20
】
09- 09
Waiting Time
Range
【
5~65
】
mSec
09- 10
BACNET Device Instance Number
Range
1~254
The Modbus communication port RJ45 and TM2 terminal (S+, S-) can be used to monitor,
control, program and trouble-shoot the inverter.
Modbus communication can perform the following operations, independent of the frequency
command selection (00-05) setting and Operation command selection (00-02) setting.
(1)
Monitoring the status from controller.
(2)
Please do not write and read the parameters by communication very often because the
EEPROM component will be damaged.
(3)
Control multi-function inputs.
Note:
When 09-01=0 (MODBUS), it can identify the communication format for ASCII and RTU. If the
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......