4
-
171
Communication Data Bit Selection(09-05)
09-05= 0:8 bits data
09-06= 1:7 bits data
RS-485 communication error detection time(09-06)
Stop selection of RS-485 communication failure(09-07)
09-07= 0:Deceleration to stop by deceleration time (00-15)
09-07= 1:Coast to stop
09-07= 2:Deceleration to stop using the deceleration time of 00-26 (emergency stop time)
09-07= 3:Keep running(warning message only, press the stop button to stop operation)
Communication fault tolerance count(09-08)
When the number of communication errors exceeds the value set in parameter 09-08 the inverter
will display the communication fault alarm.
09-09:Wait time of inverter transmission
Sets the inverter response delay time. This is the time between the controller message and the start
of the inverter response message. Refer to figure 4.3.
76
. Set the controller receive time-out to a
greater value than the wait time parameter (09-09).
09-09 setting
24 bits long
Inverter? Master
Master? Inverter
t
Commnd Message
Response Message
Figure 4.3.76 Communication message timing
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......