【0xxxb】:
PID output
【1xxxb】:
PID Frequency Command
PID target value source setting (10-00)/PID feedback value source setting(10-01).
Please confirm parameter 04-00 conform the need (0~10V or 4~20m
А
), if AI2 as PID target or PID
feedback. And switch SW2 from control board to the input type (V or I), please refer to wiring
diagram for more detail.
PID control mode (10-03)
(1)
When 10-03= xxx1b:PID is enabled,
LCD keypad will be switched automatically (16-00) and main screen monitoring displays PID
target value (12-38). Sub-screen monitoring 1 (16-01) displays PID feedback value (12-39) and
sub-screen monitoring 2 (16-02) displays frequency output (12-17). If PID is disabled, the
keypad will switch automatically to frequency command setting as the main page.
(2)
When 10-03= xx1xb:PID output is reverse.
PID output is chosen to reverse, and if PID input is negative, the output frequency of PID will
gain. On the contrary, PID output is chosen to forward, and if PID input is negative, the output
frequency of PID will decrease.
(3)
When 10-03= 0xxxb:PID output corresponds 100% to the frequency of 01-02.
When 10-03=1xxxxb, PID frequency command, it will cumulate the output percentage
of frequency command, (corresponding to 01-02 main frequency main frequency command set
by parameter 00-05/ 00-06) at the beginning of running and then start PID control.
10- 04
Feedback gain
Range
【
0.01~10.00
】
10- 05
Proportional gain (P)
Range
【
0.00~10.00
】
10- 06
Integral time (I)
Range
【
0.0~100.0
】
Sec
10- 07
Differential time (D)
Range
【
0.00~10.00
】
Sec
10- 09
PID bias
Range
【
-100~100
】%
10-14
PID integral limit
Range
【
0.0~100.0
】%
10-23
PID limit
Range
【
0.00~100.0
】%
10-24
PID output gain
Range
【
0.0~25.0
】
10-25
PID reversal output selection
Range
【0】:
Do not allow the reversal output
【1】:
Allow the reversal output
10-26
PID target acceleration / deceleration time
Range
【
0.0~25.5
】Sec
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......