4
-
182
10-30
Upper Limit of PID Target
Range
【
0 ~ 100
】%
10-31
Lower Limit of PID Target
Range
【
0 ~ 100
】%
Target value of PID will be limited to the range of upper & lower limit of PID target.
10- 33
Maximum Value of PID Feedback
Range
【
1~10000
】
10- 34
PID Decimal Width
Range
【
0~4
】
10- 35
PID Unit
Range
【
0~23
】
When 10-33 (the maximum value of PID feedback) is active, it will become 100% the
corresponding value of 10-02.
Parameter 10-34 (PID decimal width) is used for rounding up setting.
For example:set 10-34=1, it displays XXX.X ; set 10-34=2, it displays XX.XX.
Parameter 10-35 (PID unit) is selected depending on user
’
s needs.
Note:When user switches PID in LED keypad, 10-33 is required to be lower than 1000 and 10-34=1,
otherwise the keypad will show a
“
SE05
”
alarm (PID setting error).
10- 39
Output Frequency Setting of PID Disconnection
Range
【
0.00~599.00
】Hz
When PID feedback disconnection is in alarm, frequency command output depends on the
setting value of 10-39. If the warning is lifted, PID control is restored.
10- 47
Proportioanl Gain (P) of Fire Mode
Range
【0.00~10.00】
10- 48
Integral Time (I) of Fire Mode
Range
【0.0~100.0】Sec
10- 49
Differential Time (D) of Fire Mode
Range
【0.00~10.00】Sec
PID functions of ire mode, please refer to parameter group 08.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......