Group 11 Auxiliary Parameters
11-00
Direction Lock Selection
Range
【0】:
Allow forward and reverse rotation
【1】:
Only allow forward rotation
【2】:
Only allow reverse rotation
If motor operation direction is set to 1 or 2, the motor can only operate in that specific
direction. Run commands in the opposite direction are not accepted.
Forward or reverse commands can be issued via the control terminals or keypad.
Parameter 11-00 can be used in fan and pump application where reverse rotation is prohibited.
11-01
Carrier frequency
Range
【
1~16
】kHz
(1)
Setting range from 1 to 16 represents kHz.
(2)
Setting range is determined by the inverter rating (13-00) and HD/ND mode (00-27).
A low carrier frequency decreases RFI, EMI interference and motor leakage current. Please refer to
the carrier frequency table 4.3.35
Table 4.3.35 Carrier frequency settings
Carrier Frequency
1kHz
6kHz
10kHz
16kHz
Motor noise
High
------------------------
Low
Output current waveform
(similar to sinusoidal wave)
Bad
-------- Good -------
Bad
Noise interference
Low
------------------------
High
Leakage current
Low
------------------------
High
Heat loss
Low
-------------------------
High
Refer to section 3 inverter derating based on carrier frequency.
A low carrier frequency increases motor noise but reduces motor losses and temperature.
If cable length between the inverter and the motor is too long, the high-frequency leakage
current will cause an increase in inverter output current, which might affect peripheral devices.
Adjust the carrier frequency to avoid this as shown in table 4.3.36.
Table 4.3.36 Cable length and carrier frequency
Wire length
< 30m
(<98ft)
<50m
(<164ft)
<100m
(<328ft)
>100m
(>328ft)
Carrier frequency
(11-01 value)
Max value 16kHz
(11-01=16kHz)
Max value 10kHz
(11-01=10kHz)
Max value 5kHz
(11-01=5kHz)
Max value 2kHz
(11-01=2kHz)
Reduce the carrier frequency if the torque does not match the speed.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......