4
-
191
11- 61
Time Parameter of Preventing Oscillation
Range
【0~100】
Adjust the response of oscillation function. (Time parameter of adjust preventing
oscillation function delay.)
11- 62
Selection of Preventing Oscillation
Range
【0】:Mode 1
【1】:Mode 2
【2】:Mode 3
When 11-62=0 (Mode1) and 1 (Mode 2):The response to preventing oscillation is slower.
When 11-62=2 (Mode 3):The response to preventing oscillation is faster.
11- 63
Strong Magnetic Selection
Range
【0】:Disable
【1】:Enable
When 11-63=0:
It has no function of flux-strengthening, the no-load current of high speed and low speed are the
same.
When 11-63=1:
It has function of flux-strengthening, the torque of low speed is higher, but the no-load current is
also higher, it is suitable for big load in low speed.
11- 66
2/3 Phase PWM Switch Frequency
Range
【6.00~60.00】
Inverter will switch the PWM mode automatically when the output frequency is higher than
11-66.
11- 67
RPWM Frequency Bias
Range
【0~12000】
11- 68
RPWM Switch Frequency
Range
【6.00~60.00】
When inverter output frequency is higher than 11-68, the noise detection function will be enabled.
Inverter will change the ecectricmagnetic noise in operation according to the different setting value
of parameter 11-67.
Note:
When 11-02=2, the sum of 11-01+11-67 can not higher than the upper limit of carrier frequency,
please refer to the following points:
(1)
If it gets error for setting 11-01, it means 11-02=2 and the sum of 11-66+11-67 is higher than
the ipper limit of carrier frequency, please try to adjust the value of 11-02 or 11-67.
(2)
If it gets error for setting 11-67, it means 11-02=2 and the sum of 11-66+11-67 is higher than
the ipper limit of carrier frequency, please try to adjust the value of 11-02 or 11-01.
(3)
When 11-01=2, then gets error for setting 11-01 or 11-67, please check whether the sum of
11-66+11-67 is higher than the upper limit of carrier frequency.
(4)
If it gets error for setting 11-02=2, it means the sum of 11-66+11-67 is higher than the upper
limit of carrier frequency, please adjust the value of 11-01 or 11-67 for suitable range, then set
11-02=2.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......