4
-
198
13- 08
Restore factory setting / Initialize
Range
【1】:2 wires initialization (50Hz) (220V/380V)
【2】:2 wires initialization (60Hz) (220V/380V)
【3】:2 wires initialization (50Hz) (230V/400V)
【4】:2 wires initialization (60Hz) (220V/460V)
【5】:2 wires initialization (50Hz) (220V/415V)
【6】:2 wires initialization (60Hz) (230V/400V)
【7】:2 wires initialization (50Hz) (220V/440V)
【8】:2 wires initialization (60Hz) (220V/440V)
【9】:2 wires initialization (60Hz) (220V/380V)
【10】:2 wires initialization (60Hz) (220V/380V)
【1112】:PLC initialization (RESET)
Use parameter 13-08 to initialize the inverter to factory default. It is recommended to write down
the modified parameters before initializing the inverter. After initialization, the value of 13-08 will
return to zero automatically.
13-08=1:2 wires initialization (220V/380V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2)
Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 380V (440V calss).
(3)
When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=2:2 wires initialization (220V/380V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2)
Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 380V (440V calss).
(3)
When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=3:2 wires initialization (230V/400V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2)
Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 400V (440V calss).
(3)
When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=4:2 wires initialization (230V/460V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2)
Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 460V (440V calss).
(3)
When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=5:2 wires initialization (220V /415V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2)
Inverter input voltage (01-14) is automatically set to 220V (220V calss) or 415V (440V calss).
(3)
When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......