4-204
Group 16 LCD Function Group
16- 00
Main Screen Monitoring
Range
【
5~43
】
16- 01
Sub-Screen Monitoring 1
Range
【
5~43
】
16- 02
Sub-Screen Monitoring 2
Range
【
5~43
】
At power-up the inverter shows two monitor section on the display, main monitor section and
the sub-screen monitor section (smaller font).
Choose the monitor signal to be displayed as the main-screen monitor screen in parameter
16-00, and the monitor signals to be displayed on the sub-screen monitor in parameters 16-01
and 16-02, similar to monitor parameters 12-5~12-43.
16- 03
Display unit
Range
【
0
】:
Frequency display unit is Hz (Resolution is 0.01Hz)
【
1
】:
Frequency display unit is % (Resolution is 0.01%)
【
2
】:
Frequency display unit is RPM
【
3~39
】:
Reverse
【
40~9999
】:
100% is XXXX with no decimals (integer only)
【
10001~19999
】:
100% is XXX.X with 1 decimal
【
20001~29999
】:
100% is XX.XX with 2 decimals
【
30001~39999
】:
100% is X.XXX with 3 decimals
16- 04
Engineering Unit
Range
【
0
】:
No Unit
【
1
】:
FPM
【
2
】:
CFM
【
3
】:
PSI
【
4
】:
GPH
【
5
】:
GPM
【
6
】:
IN
【
7
】:
FT
【
8
】:
/s
【
9
】:
/m
【
10
】:
/h
【
11
】:
°F
【
12
】:
inW
【
13
】:
HP
【
14
】:
m/s
【
15
】:
MPM
【
16
】:
CMM
【
17
】:
W
【
18
】:
kW
【
19
】:
m
【
20
】:
°C
【
21
】:
RPM
【
22
】:
Bar
【
23
】:
Pa
Display unit of digital operator(16-03)
Set the units of the following items to be displayed, the frequency reference (05-01, 00-18,
06-01~06-15) and the monitoring frequency 12-16, 12-17 (Output frequency).
Display unit of engineering (16-04)
When 16-03 = 00040-39999, engineering units are enabled. The displayed set range and the
frequency range of unit (05-01, 06-01~06-15) as well as the monitoring frequency (12-16, 12-17)
are changed by parameters 16-04 and 16-03.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......