4-229
23- 04
Pump Pressure Command Source
Range
【0】: Set by 23-02
【1】: Set by AI
Pressure command source is given the value set by 23-02 (Operation Pressure Setting) or AI.
Refer to parameter 10-00 for the setting of AI terminal.
23- 05
Display Mode Selection *2
Range
【0】: Display of Target and Preesure Feedback
【1】: Only Display Target Pressure
【2】: Only Display Pressure Feedback
This function can have the common display of target & feedback pressure or display separately
When 23-05=0000, LED keypad displays pressure setting value and pressure feedback
Two-digit in the left is the pressure value setting and two-digit in the right is the pressure feedback
value in the seven-segment monitor. When 23-00=2 (HVAC), the unit will be multiplied by 1000
times. If the display value is 5.0, it means 5000GPM
When 23-05=0001:LED keypad only displays the pressure setting value.
When 23-05=0002:LED keypad only displays the pressure feedback value.
Note:
If Pump mode is used LED keypad, parameter 23-03 is required to ≦ 99.0 PSI.
If Pump mode is used PID mode, the value of 10-33 is required to ≦ 999 and 10-34=1.
23- 06
Proportion Gain (P)
Range
【0.00~10.00】
23- 07
Integral Time (I)
Range
【0.0~100.0】Sec
23- 08
Differential Time (D)
Range
【0.00~10.00】Sec
Fig. 4.4.103 Diagram of pressure feedback value
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......