4-231
23- 11
Sleep Time of Constant Pressure
Range
【0.0~255.5】Sec
When the inverter finishes counting the sleep time (23-11), the output frequency falls
downward at the deceleration time (00-15) and gets into sleep status. Parameter 23-10 (sleep
frequency of constant pressure) is dedicated by the pump and it is not applied to parameter
10-17 (start frequency of PID sleep).
Fig. 4.3.103 Diagram for stop time of constant pressure
23- 12
Maximum Pressure Limit
Range
【0.00 ~ 650.00】PSI
It is convenient for user to limit maximum pressure. When pressure feedback value is higher
than maximum pressure limit, the inverter displays warning signal and then stops.
23- 15
Minimum Pressure Limit
Range
【0.00 ~ 650.00】PSI
It is convenient for user to limit minimum pressure. When pressure feedback value is lower than
minimum pressure limit, the inverter displays warning signal and then stops.
Fig. 4.3.104 Diagram for pressure feedback limit
Note:
The pressure under the control of PID is between the maximum pressure limit (23-12) and minimum
pressure limit (23-15).
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......