4- 245
4.4.3
Application functions
1.
Counter Function
Counter mode (1 ~ 4)
UP/Down counting modes can be set by (I1 ~ f8).
OFF: Count up (0, 1, 2, 3…)
ON: Count down (…3,2,1,0)
Use (I1~f8) to reset counting value
ON: Internal count value is reset and counter output
is OFF
OFF: Internal counter value retained
Internal counter value
Counter compare value (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7,constant)
Counter output (C1 to C8, there are a total of 8 counters)
Counter modes
:
Mode 1: Counter value is locked to the set value.
The value will not be retained when the power is cut off.
Mode 2: Counter value is not locked.
The value will not be retained when the power is cut off.
Mode 3: Counter value is locked.
The value will be retained when the power is cut off.
Mode 4: Counter value is not locked.
The value will be retained when the power is cut off.
(1)
Counter mode 1